AINTENANCE

 

 

There is no regular maintenance required of the PSU as the microcontroller performs regular health checks of the battery and output voltage. 

However, reference should be made to the battery manufacturer’s documentation to determine typical / expected battery life with a view to 
periodic replacement of the battery.  

If the output of the PSU fails the cause of the failure should be investigated e.g. short circuit load, connection of a deeply discharged battery. The fault 
should be rectified before restoring power to the PSU. The following fuses may need to be replaced. Ensure the correct fuse rating and type is used. 
Load Output Fuse 

 

F5A 20mm, 250Vac glass 

Internal Mains Fuse   

T3.15A 20mm, 250Vac HBC 

Battery Fuse 

 

F5A 20mm, 250Vac glass 

CAUTION 

Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries according to the 

battery manufacturer’s instructions and all local and national regulations 