side 49
•
Result is displayed afterwards:
Fig. 3.12a Example of trip-out time
measurement result
Fig. 3.12b Example of measurement
result – RCD did not trip-out
Uc.....Contact voltage.
•
Disconnect the instrument from RCD under test.
Note: For safety reason, contact voltage is automatically measured before trip-out time is
measured. As the selective type of RCDs include integrator, it is necessary to wait some
time before the integrator sets to default. This is why the measuring process inserts a
pause 30 s for selective RCDs. The remaining time is displayed as count down from 30 to
1:
Fig. 3.13 Example of count down for
Trip-out current I
\
•
Set
I
\
function by the
FUNC
key.
You can set the nominal differential current by the
I
Δ
N
key.
You can set the RCD type by the
TYPE
key.
Fig. 3.14 Example of settings for trip-out current measurement