ELKHART BRASS URFA-20 Скачать руководство пользователя страница 4

 

B.  STANDPIPE SYSTEM  
 

The models URFA-25-2.5 and URFA-20-2.5 valves are most commonly used in standpipe 
systems.  The URFA-25-2.5 valves have a male hose thread outlet for connecting to fire 
suppression hose.  When hose racks are used, the URFA-20-2.5 can be utilized along with a 
special hose nipple for support of the rack.  The URFA valves are Listed by Underwriters 
Laboratories as Standpipe Equipment Pressure Reducing Devices (VUTX).  Requirements for 
installation of pressure reducing valves in standpipe systems are given in Section 5-8 of NFPA-
14, Standard for the Installation of Standpipe Hose Systems, 1993 Edition.   
 
 

INSTALLATION REQUIREMENTS 
 

A.  AUTOMATIC SPRINKLER SYSTEM  

 

1.  To permit easy replacement or repair of valve, pipe unions or rubber gasket 

mechanical couplings should be installed immediately upstream or downstream of 
each URFA valve. 

2.  A relief valve of not less then ½ inch size is to be installed on the downstream side 

of each URFA valve 

3.  Pressure gauges are to be installed on the inlet and outlet side of each pressure- 

reducing valve 

4.  Valve adjustment setting should be selected to provide an outlet pressure not 

exceeding 165 psi at the maximum inlet pressure 

5.  Upon system completion, each Valve must be tested under both flow and no-flow 

conditions to verify that static residual outlet pressures and flow rates satisfy system 
design requirements.  See Section 8-2.5 NFPA 13 for more information on 
mandatory flow and no-flow test requirements. 

 
B. STANDPIPE SYSTEM 
 

1.  The  URFA-25-2.5 can be used for both Class I and Class III service.   
2.  NFPA 14 requires that hose valve outlet pressures for Class I and Class III service 

be no greater then 175 psi. and no less then 100 psi.  When permitted by the 
authority having jurisdiction, pressures less then 100 psi may be allowed, but in no 
cases shall the valve discharge pressure be less then 65 psi 

3.  Upon system completion, each valve must be tested under both flow and no-flow 

conditions to verify that static and residual outlet pressures and flow rates satisfy 
system design requirements.  See Section 8-5.5 of NFPA 14 for more information 
on required flow and no-flow testing. 

 

 

CONSTRUCTION & OPERATING PRINCIPLE 

 
The URFA is a field adjustable pressure-reducing valve, which utilizes a hydraulic piston and 
cylinder assembly within the valve lower bonnet to allow the valve to self-throttle in response 

Содержание URFA-20

Страница 1: ...URFA 20S 2 5 URFA 20 2 5 URFA 25 2 5 INSTALLATION AND OPERATING INSTRUCTIONS FOR FIELD ADJUSTABLE PRESSURE REDUCING CONTROLLING VALVES URFA 20 2 5 MODEL SHOWN...

Страница 2: ...UTOFF OPEN CLOSE INDICATION SUPERVISORY SWITCH ENCLOSURE SUPERVISORY SWITCH PLUG TAMPER RESISTANT COVER TAMPER RESISTANT SCREW INDICATION LABEL UPPER BONNET ADJUSTMENT CYINDER HOLE BONNET NUT LOWER BO...

Страница 3: ...s where supply riser pressures exceed 175 psi The URFA valves are Listed by Underwriters Laboratories as Special System Water Control Valves Pressure Reducing and Pressure Control Type VLMT and also m...

Страница 4: ...ld be selected to provide an outlet pressure not exceeding 165 psi at the maximum inlet pressure 5 Upon system completion each Valve must be tested under both flow and no flow conditions to verify tha...

Страница 5: ...independent operation of the valve stem from the manual close push rod this allows for the operator to bypass the large torque required to overcome the stiffness of the adjustment spring INSTALLATION...

Страница 6: ...the pump churn pressure less the elevation loss 7 To determine the valve static outlet pressure refer to the appropriate static chart Locate the valve static inlet pressure on the vertical axis of th...

Страница 7: ...valve is not manually in the fully opened position refer to NFPA 13 for more details on supervisory requirements An optional supervisory switch assembly with UL approval for use with URFA valves is av...

Страница 8: ...gnal Also ensure that the manual handwheel may be fully closed without interference from the supervisory switch assembly VALVE CARE MAINTENANCE URFA valves require minimal maintenance However a routin...

Страница 9: ...ve incorrect valve setting it should be reset to the proper setting and undergo flow and no flow testing to verify proper pressure reduction is obtained Flow test results should be compared to previou...

Отзывы: