IMPORTANT NOTICE
All wiring should be carried out by a competent person or a qualified electrician and should be fitted to IEE 17th Edition Wiring regulations BS7671:2008.
The circuit should be isolated before carrying out any work. Failure to adhere to the instructions will invalidate the warranty.
diagram 3
Please note that the black bar denotes the position of the dip switch.
Dip switch 4 is only used for Setting Automatic (150 Lux) or Manual Lux ONLY.
4.
3.
2.
1.
4.
3.
2.
1.
4.
3.
2.
1.
4.
3.
2.
1.
4.
3.
2.
1.
ON DIP
ON DIP
ON DIP
ON DIP
ON DIP
Manual Lux
2 mins
5 mins
10 mins
15 mins
4.
3.
2.
1.
4.
3.
2.
1.
4.
3.
2.
1.
ON DIP
ON DIP
ON DIP
20 mins
30 mins
60 mins
LIVE IN
LIVE OUT
NEUTRAL
LIVE IN
LIVE OUT
NEUTRAL
LUX LEVEL
ADJUSTMENT
SENSITIVITY
ADJUSTMENT
DIL
SWITCHES
Wiring diagram for a single unit.
Wiring diagram for wiring multiple devices together.
LIVE IN
LIVE OUT
NEUTRAL
fitting and operating instructions
ceilingmount
pir
IMPORTANT NOTICE
Call +44 (0) 1675 468222 or visit www.elkay.co.uk
IMPORTANT NOTICE
All wiring should be carried out by a competent person or a qualified electrician and should be fitted to IEE 17th Edition Wiring regulations BS7671:2008.
The circuit should be isolated before carrying out any work. Failure to adhere to the instructions will invalidate the warranty.
IT IS ESSENTIAL THAT YOU FOLLOW CLOSELY STEPS 1 TO 8 OF
THE MOUNTING AND INSTALLATION INSTRUCTIONS BELOW.
FAILURE TO DO SO WILL INVALIDATE THE WARRANTY.
Mounting and Installation
Step 1
- Please ensure that you position the PIR in the correct
place by reading the Positioning section of these instructions.
For flush mounting cut a clean hole measuring 64mm in
diameter in the chosen area for the sensor. For surface
mounting attach surface mount cup to ceiling with
connection cable hanging through the middle. Seal any large
holes on ceiling to prevent air current activation.
Step 2
- Ensure that the mains power to the circuit is
switched off. Ensure terminal cover and cable clamp are
correctly fitted with screws supplied. Place the Live In into the
Terminal marked Live In and the switched Live Out into the
Live Out terminal. Place the neutral into the connection
marked N for neutral. Please note that it is essential that the
Live In wire and the switch Live Out and Neutral are identified
prior to commencing installation. To connect multiple units
connect the live switch live and neutrals as shown in Diagram
2. Turn off mains supply for installation as live working is not
recommended and can damage the unit.
Step 3
- For flush mounting fold the two arms up into the
vertical position and insert unit into the hole. Release unit
ensuring arms are securely in place. For surface mounting fit
surface mount cup onto ceiling or conduit terminal box and
return connected PIR into surface mount cup.
Step 4
- Remove the fascia by turning anti-clockwise to show
the lux pot, sensitivity pot and the timing/lux Dip switches.
Please adjust the Lux Level and Sensitivity potentiometer
gently without force as this is a sensitive electronic part. After
adjustment please wait 30 seconds for changes to take
effect. It is recommend product is set up initially using the 10
secs walk test mode.
Step 5
- To set Auto Lux (150 Lux), switch Dip switch 4 to the
ON position. This will allow activation of the PIR from Dusk
until Dawn only. To set manually then put dip switch 4 off
and use the potentiometer to adjust to desired lux level
setting. All the way to the plus setting will allow the PIR to
switch day and night. All the way to the minus sets the timer
to ZERO lux and effeftively switches off the PIR. To set
manually you will need to be present at dusk (See Diagram 3).
Step 6
- To adjust sensitivity turn anti-clockwise to the High
(H) setting to increase sensitivity and clockwise to the Low (L)
to decrease sensitivity.
Step 7
- To set time please utilise the dip switch timing
diagram above. The black bar denotes dip switch position.
Replace fascia ring by turning anti clockwise (See Diagram 4).
Step 8
- The PIR will take approximately 2½ minutes to
initialise and will flash rapidly after the mains power is first
applied to allow the sensor to learn its environment. The load
will be ON after 7 seconds initially, then switch off after 2½
minutes if there is no detection in the zones.
Operation
In standard operation the PIR will now sense infra red heat
when a person or source of heat passes through the
detection zone. Each time the PIR is triggered it will reset the
timer back to the start of the timing period. The unit will then
wait 5 seconds before allowing the PIR to sense and re trigger
the timing period again.
If no one is present in the room or the detection zone is not
passed through, during its set time period, the timer will time
out, turning off the lights or appliance.
The PIR unit will only trigger the lights or appliance if the
ambient light level is below that set on the lux level
adjustment.
4.
3.
2.
1.
ON DIP
Test Mode
10 Secs
4.
3.
2.
1.
ON DIP
Auto Lux
diagram 2
diagram 4
Time Settings (Test Mode to 60 mins)
RPM 305
There are now 2 neutral terminals - one or both can be used.
Please note Elkay ceilingmount PIR’s have ONLY one neutral terminal.