4 AMP POWER SUPPLY

ELK-967 POW ER DISTRIBUTION MODULE

POWER
OFF

SW1

14.

5V

D

C

 I

N

+

-

+12V

OUTPUT 1

NEG

+12V

OUTPUT 2

NEG

+12V

OUTPUT 3

GRD

NEUTRL

LINE

WARNING

SHOCK

HAZARD

AC

POWER
ON LED

+

-

N
O

COMNC

-

+

ELK-912 RELAY

Voltage is lost here during

AC Power Failure which will

cause the relay to drop out

and activate the sounder

BLACK

RED

12 Volt
Battery

12 VOLT

SOUNDER

LOAD 1

LOAD 2

ELK-P412 Installation & Hookup Examples

APPLICATION: AC Power Failure Indicator

This hookup will activate a 12 volt sounder if AC Power
is lost.The ELK-912 relay will be energized while AC
Power is ON. If AC Power is lost then the relay will turn
off closing the COM and N.C. contacts to activate the
sounder. The sounder is powered from the Battery.

APPLICATION: 4 AMP HOOKUP

Parallel any two outputs together for heavy loads up
to 4 AMPS continuous. The third output can not be
used in this configuration.

AC

INPUT

NEG

BATTE

RY

+

-

POWER
ON

POWER ON LEDS

L N

-V +V

DC

OUTPUT

EARTH

GROUND

4 AMP POWER SUPPLY

ELK-967 POW ER DISTRIBUTION MODULE

POWER
OFF

SW1

14.

5V

D

C

 I

N

+

-

+12V

OUTPUT 1

NEG

+12V

OUTPUT 2

NEG

+12V

OUTPUT 3

GRD

NEUTRL

LINE

WARNING

SHOCK

HAZARD

AC

POWER
ON LED

+

-

BLACK

RED

12 Volt
Battery

4 AMP LOAD

(CONTINUOUS)

OUTPUT 3 CAN NOT

BE USED IN THIS
CONFIGURATION

BLOCK DIAGRAM of DC Output Terminals

Each output can provide up to 2.5 Amps each (fused at
2.5 amps). However, the combined load from all outputs
must not exceed 4 Amps continuously.

+

-

CONNECT LOADS TO EACH OUTPUT OR COMBINE

OUTPUTS TO SUPPLY MORE CURRENT

 (DO NOT TO EXCEED 4 AMPS TOTAL)

2.5 AMP

FUSE (PTC)

4 AMP POWER SUPPLY and BATTERY

(CURRENT DRAW OVER 4 AMPS WILL COME FROM THE BATTERY)

2.5 AMP

FUSE (PTC)

2.5 AMP

FUSE (PTC)

OUTPUT 1

UP TO

2.5 AMPS

-

-

+

+

OUTPUT 2

UP TO

2.5 AMPS

OUTPUT 3

UP TO

2.5 AMPS

APPLICATION: DUAL 2 AMP HOOKUP

For two separate 2 Amp continuous loads. DO NOT
EXCEED 4 AMPS TOTAL. The third output can not
be used in this configuration.

AC

INPUT

NEG

BATTE

RY

+

-

POWER
ON

POWER ON LEDS

L N

-V +V

DC

OUTPUT

EARTH

GROUND

4 AMP POWER SUPPLY

ELK-967 POW ER DISTRIBUTION MODULE

POWER
OFF

SW1

14.

5V

D

C

 I

N

+

-

+12V

OUTPUT 1

NEG

+12V

OUTPUT 2

NEG

+12V

OUTPUT 3

GRD

NEUTRL

LINE

WARNING

SHOCK

HAZARD

AC

POWER
ON LED

BLACK

RED

12 Volt
Battery

OUTPUT 3 CAN NOT

BE USED IN THIS
CONFIGURATION

+

-

2 AMP LOAD

(Sirens,etc)

+

-

2 AMP LOAD

(Cameras, etc)

Отзывы: