8 - EN
V800
Terminal
Label
Description
Notes
Par. / Notes
14
DI1
Digital input 1
it is strictly prohibited
to connect the Digital
Input to a power source
H11, H30
15
DI2
Digital Input 2
H12, H30
16
DO2
Open Collector Output
H22
17
GND
Ground
18
AO1
Analogue Output
repeat in 0-10V scale VO valve output (terminals 11-12)
19
AI1
Analogue Input 1
overheating probe
H00 configurable NTC/4...20mA*
20
5V
c
Probes Power Supply
**Power supply for ratiometric probe (terminal 21)
21
AI2
Analogue Input 2
saturation probe
H01 configurable NTC/4...20mA*/0-5V (ratiomet-
ric)**/ LAn (remote, shared pressure transducer)
22
12V
c
Probes Power Supply
*Power supply for 4...20mA current input (terminals 19/ 21)
23-24
LAN
Powered serial port
ID985/V connection
DMI/CC
Serial port for connection to
• USB Copy Card / • IWK/V
See DipSwitch
TTL
Serial port for connection
to Televis / Modbus
PtS, dEA, FAA, PtY, Ptb