background image

9MA10011

30/52

Example of print

Description

Connector/Terminal: AI01

Probe type: 4..20 mA

Unit of Measure : Bar

Decimal Points : 1

Probe name: CONDENSING

Min. value :      0.0

Max. value :     30.0
Alarm Output :  1

Delay (m) :  0

Alarm hysteresis:      0.1

Posit. Emerg. :     10.0

Posit. Delay:      8.0

Negat. Delay:      0.0

Negat. Emerg. :      0.0
Analogue input : 2

---------------------------

Connector/Terminal: AI02

Probe type: 4..20 mA

Unit of Measure : Bar

Decimal Points : 1

Probe name: SUCTION

Min. value :     -0.5

Max. value :      7.0
Alarm Output :  1

Delay (m) :  0

Alarm hysteresis:      0.1

Posit. Emerg. :      7.0

Posit. Delay:      6.5

Negat. Delay:      0.0

Negat. Emerg. :      0.0
Digital input : 1

---------------------------

• …and for Analogue Alarms

Example of print

Description

Connector/Terminal: AI03

 Default State : N.A.

Name : N0-D1

Alarm Output :  1

Delay (m) :  0

Digital input : 2

---------------------------

• Settings for Digital Inputs and 

• Digital alarms

Connector/Terminal: AI04

 Default State : N.C.

Name : N0-D2

Alarm Output :  1

Delay (m) :  0

End of print

At the end the following message appears

End of print

Содержание Memory 1000

Страница 1: ...English Memory 1000 Multichannel data logger 9MA10011...

Страница 2: ...9MA10011 2 52...

Страница 3: ...2 6 Printer 25 7 Download data with SD Card 32 8 Memory 1000 Data Manager 33 9 Electrical connections 36 10 Mechanical assembly 41 11 Specifications 42 12 Applicable Standards 44 13 Use 46 14 Responsa...

Страница 4: ...9MA10011 4 52...

Страница 5: ...ia RS 485 network or RadioAdapter wireless modules Manages all aspects of network controller alarms 12 months data logging capacity A model to fit all application requirements The Memory 1000 wall mou...

Страница 6: ...the main user interface and shows various different types of information Default main views i e values of data read Selection menu 2 1 Keys There are 8 keys on the front panel Each key see the two ta...

Страница 7: ...ss once press and release Key associated function Menu Comments Only key enabled in Main Display Menu Opens general menu Opens menus Esc ape function goes back to previous level See General Menu NOTE...

Страница 8: ...ONBOARD P6 18 4 ONBOARD P7 2 0 ONBOARD P8 2 3 ONBOARD DI Not active ONBOARD D2 Not active The Main Display on the LCD when no keys pressed have been Date and current time dd mm yy and hh mm formats r...

Страница 9: ...is network resources see section 4 5 Network 1 State active not active Alarm condition The number of resources depends on the system settings and model 2 3 1 3 First switch on This page appears when t...

Страница 10: ...u The advanced PSW range 0 65535 allows you to restrict access to the Adv Configuration menu N B Default values 0 for all three passwords In the example the Advanced PSW is set to 99 Obviously the 3 p...

Страница 11: ...tivate REC On automatically at the current settings in the controller 2 4 3 2 Data See Printer section 2 4 4 3 Alarms See Alarms section 2 4 5 4 Std Configuration See Standard Configuration section 2...

Страница 12: ...arm indicates the number of the active alarm highlighted total number of active alarms In the example 001 004 1 of 4 active alarms the highlighted alarm is the onboard digital input 1 The list of all...

Страница 13: ...gating the menu or while printing 4 STANDARD CONFIGURATION From the General menu use the UP and DOWN keys to select option 5 then press the OK key to open the Standard Configuration menu The following...

Страница 14: ...aph First switch on FIRST ACCESS Language Italian AAAA MM GG date HH MM SS hour Period REC min 000 EN12830 24h 30s Num of probes used 8 Num of digits used 2 Reset system 0000H NOTE unlike the first re...

Страница 15: ...the degree of conformity with UNI EN 12830 see First Switch On 4 3 Not used 4 4 Onboard resources 4 4 ONBOARD RESOURCES 4 4 0 General Info 4 4 1 Analogue Inputs 4 4 2 Analogue Alarms 4 4 3 Digital Inp...

Страница 16: ...Value 20mA 30 0 Offset 0 7 Read 13 3 View Text YES Index Input Index Name Name of Input The default names are ONBOARD P1 ONBOARD P8 and can be modified as required max 10 characters Probe type set aut...

Страница 17: ...associated 1 Output 1 Delay min minutes delay before activating Alarm Output 0 240 min Positiv Emerg upper threshold and immediate generation of alarm when limit exceeded Positiv Delay upper threshold...

Страница 18: ...d as a result of previous Default State States are Closed or Open View Text if YES then the value is entered in a list of elements to be viewed in Default View Read only information 4 4 4 Digital alar...

Страница 19: ...ble Eliwell Televis devices connected via serial port RS485 to Memory 1000 4 5 0 Network Mode 4 5 0 NETWORK 1 MODE Change data Delete Network configuration Network type Televis Network address 14 14 M...

Страница 20: ...he network and the Analogue Inputs read by the network Example 4 devices and 6 Inputs 3 the first see Device Analogue Inputs section 2 the second 1 the third 4 5 4 NETWORK 1 GENERAL Total no of units...

Страница 21: ...the Televis Address of the device in Televis F D format by a Progressive Number and by the Probe Name Select the input for example the first one with index 0 using the Up and Down keys and press OK A...

Страница 22: ...ibed in the section entitled Standard Configuration The menu is password protected see the section on how to set the Password We recommend you protect the menu with a password that is known to authori...

Страница 23: ...D IN ALARM On 5 1 2 Alarm output Out1 Enable output Enabled Not enabled Output off off during acknowledgment Output off on if data logging is NOT active NA or NC contact 5 1 2 DIGITAL OUTPUT 1 Enabled...

Страница 24: ...k error value 0 one attempt 3 four attempts Alarm time s Network 1 2 values from 10 to 300 seconds in 10 second steps sets the frequency with which the Datalogger runs a full network scan of alarm sta...

Страница 25: ...nter status Icon Colour Permanently on Blinking Printer status Green Printer switched on from key Printing Print job suspended manually from key No paper Printer error 6 3 Printer Configuration The fo...

Страница 26: ...urposes along with associated recording intervals Start recording time Rec On is indicated on the left and end recording time Rec Off on the right N B If the device is currently recording data the las...

Страница 27: ...nu 2 3 Print Text allows you to print data for onboard network resources as text Same configuration as menu 2 2 there is no Type of data to print option see section 5 2 Printer 6 5 Examples of prints...

Страница 28: ...sampling frequency Limitation in the Y scale range for graphical print Memory 1000 may not print correctly the header of the Y axis when the total number of digits including the sign composing the min...

Страница 29: ...following message appears End of print 6 5 3 Example of Print Onboard Resource Configuration Example of print Description DATA LOGGER Page 01 12 02 2007 Time 13 56 Device Code 0000H 004CH Print Device...

Страница 30: ...nit of Measure Bar Decimal Points 1 Probe name SUCTION Min value 0 5 Max value 7 0 Alarm Output 1 Delay m 0 Alarm hysteresis 0 1 Posit Emerg 7 0 Posit Delay 6 5 Negat Delay 0 0 Negat Emerg 0 0 Digital...

Страница 31: ...s MSK VER codes etc Analogue Input 1 Probe Enabled YES NO UM decimal points etc Analogue Input 2 Analogue Input 3 Unit Index 2 Analogue input 1 Analogue Input 2 Etc End of print At the end the followi...

Страница 32: ...ig 1 Memory 1000 will recognize it automatically and the words SD CARD In will appear on the display Once the controller has recognized it and checked it has been formatted it will immediately start t...

Страница 33: ...m requirements Hardware Minimum configuration Operating System CD MEMORY 1000 DATAMANAGER Pentium 200 MHz RAM 256 MB Available HDU 300MB 1 free COM Windows 98 Windows 2000 Windows XP PRO Windows Vista...

Страница 34: ...ms recorded by Memory 1000 in the selected period Control panel configuration parameters to export data and selection of application language b Exit program 8 6 Barra di navigazione Icon Description S...

Страница 35: ...le scv table in accordance with settings in control panel bmp graph Graphs Tables Icon Description Screen Print Print data Graphs Tables Zoom To enlarge a portion of the graph x axis only Graphs Confi...

Страница 36: ...he build up of static electricity 9 1 1 Power supply High voltage output relay Do not exceed the maximum permitted current for higher loads use a contactor with sufficient power capacity Important Mak...

Страница 37: ...section cable plus braiding i e Belden cable model 8762 with PVC sleeve 2 conductors plus braiding 20 AWG nominal capacity between 89pF conductors nominal capacity between a conductor and 161pF shiel...

Страница 38: ...ber of analogue inputs digital inputs and alarm outputs depends on the Memory 1000 model see section Annexe A Models and Accessories Modelli Base Modelli Standard sonde NTC Modelli Standard sonde NTC...

Страница 39: ...2 A SPDT 250Va 6 7 8 9 AI 1 AI 2 Input for NTC probe 4 20mA current input 6 12V 7 signal 10 11 AI 3 Input for NTC probe 12 13 AI 4 Input for NTC probe 14 15 AI 5 Input for NTC probe 16 17 AI 6 Input...

Страница 40: ...li Power Supply from da Memory 1000 6 8 7 9 12 IN 12 IN 10 GND AI1 AI2 12V T RH GND 3 wires 3 fili Power Supply from da Memory 1000 Probe Sensore Signal Segnale RH GND 6 8 7 9 12 IN 12 IN 10 GND AI1 P...

Страница 41: ...e out the screws and open the door Drill holes in the backplate at the top or bottom to pass the wires through See the example in figure 2 Fig 1 Fig 2 Screw the backplate to the wall using 4 screws no...

Страница 42: ...output All models Digital inputs DI1 DI2 2 no voltage digital inputs 5mA contact current All models Analogue inputs 4 20mA AI1 AI2 2 4 20 mA current inputs 1 full scale accuracy 0 1 C bar resolution...

Страница 43: ...mory 1085 F 2AI Memory 1180 15F 2AI Memory 1185 15F 2AI Buzzer All models Terminals Removable screw connector pitch 5 0mm All models Container PC ABS plastic resin with V0 flammability rating All mode...

Страница 44: ...er to guarantee the recordings according to EN12830 it is suggested to operate as following set a recording interval of 15 minutes and after a print process is terminated wait at least 20 minutes befo...

Страница 45: ...e Type A climatic environment and temperature test under data logger storage and transport conditions Electrical disturbances and radiated electromagnetic field susceptibility compliant with EN 61326...

Страница 46: ...on uses other than those specified and in particular which do not comply with the safety requirements set out in the regulations and or stated herein use on panels that do not provide adequate protect...

Страница 47: ...10 2 6 2 2 YES YES RS485 expandable models with or without printer 1180 15F 2AI 10 2 6 2 2 YES 15 controllers YES 1185 15F 2AI 10 2 6 2 2 15 controllers YES NOTES 1 2 fixed NTC the rest can be configu...

Страница 48: ...llowing parameters for 04mA 0 5 for 20mA 7 See par 4 4 1 Humidity transducers EWHS 280 SN560000 Relative humidity transducer measurement range 15 90 Set the following parameters for 04mA 20 for 20mA 1...

Страница 49: ...guration key Name Part number Description NOTE Software Tools Memory1000 Data Manager 5555966 It comes with MS Windows compatible data logging software to export save and view data in table and graph...

Страница 50: ...2LX R U RH 4 20mA 132 23 1 4 20mA 0 10V 1 230V IR12I00XBD700 IC 915LX R H D RH 4 20mA 132 23 1 4 20mA 0 10V 2 230V 17 ANNEXE B ELIWELL INSTRUMENTS 17 1 Eliwell devices Part number Item MSK VER Number...

Страница 51: ...LX 2Hp RTC HACCP BUZ V2 0 390 06 3 NTC PTC 3 230V RCP3UDTX0H700 EWRC 500LX 2Hp RTC HACCP BUZ 289 12 3 NTC PTC 5 230V RCP3UDTX0H710 EWRC 500LX 2Hp RTC HACCP BUZ V2 0 390 06 3 NTC PTC 5 230V RCP3UDTX1H7...

Страница 52: ...trols S r l Via dell Industria 15 Zona Industriale Paludi 32010 Pieve d Alpago BL Italy Telephone 39 0437 986 111 Facsimile 39 0437 989 066 Sales 39 0437 986 100 Italy 39 0437 986 200 other countries...

Отзывы: