TECHNICAL DATA
Front protection: IP65.
Casing: PC+ABS UL94 V-0 resin plastic
body, polycarbonate front, thermoplastic
resin buttons.
Dimensions: front 74x32 mm, 60 mm
depth.
Mounting: on panel, with drilling template
71x29 mm (+0.2/-0.1 mm).
Operating temperature: -5…55 °C.
Storage temperature: -30…85 °C.
Usage ambient humidity: 10…90 % RH
(non-condensing).
Storage ambient humidity: 10…90% RH
(non-condensing).
Display range: -50…110 (NTC); -55…140
(PTC) °C without decimal point (parameter
selectable), on display 3 sign.
Analogue inputs: three PTC or NTC inputs
(parameter-selectable).
Digital inputs: 2 voltage-free parameter-
configurable digital inputs.
Serial: TTL for Televis or Copy Card con-
nection.
Digital outputs:
4 outputs on relays: first output (A) SPDT
8(3)A 250V
a
, second and third output (B-
C) SPST 8(3)A 250V
a
, fourth output (D)
SPST 5(2)A 250V
a
.
Measurement range: from -55 a 140 °C.
Accuracy: better than 0.5% of bottom scale
+1 digit.
Resolution: 1 or 0.1 °C.
Consumption: 3 VA.
Power supply: 12 V
a
/
c
±10% 50/60 Hz
Caution: check the power supply specified
on the instrument label; for information
on relay capacity and power supplies con-
tact the Sales Office.
ID 985 LX Fan Condenser
5/11
DISCLAIMER
This document is exclusive property of Eliwell & Controlli S.r.L. and
cannot be reproduced and circulated unless expressly authorized
by Eliwell & Controlli S.r.L.. Although Eliwell & Controlli S.r.L. has
taken all possible measures to guarantee the accuracy of this doc-
ument, it declines any responsibility for any damage arising out of
its use.
The same applies to any person or company involved in preparing
and writing this manual. Eliwell & Controlli S.r.L. reserves the right
to make any changes or improvements without prior notice and at
any time.
NOTE: The technical characteristics in this document concerning measurements (range, accuracy, resolution, etc.) refer to
the instrument in the strictest sense and not to any accessories provided such as probes, for example.
This means that an error introduced by the probe is added to any error that is in the instrument.
RESPONSIBILITY AND RESIDUAL RISKS
Eliwell & Controlli S.r.L. shall not be liable for any damages deriv-
ing from:
• installation/use other than that prescribed and, in particular,
which does not comply with the safety standards specified in the
regulations and/or those given herein;
• use on boards which do not guarantee adequate protection
against electric shock, water or dust when assembled;
• use on boards which allow dangerous parts to be accessed
without the use of tools;
• tampering with and/or alteration of the product;
• installation/use on boards that do not comply with the stan-
dards and regulations in force.
CONDITIONS OF USE
PERMITTED USE
For safety reasons the instrument must be installed and used in accordance with the instructions supplied. Users must not be able to
access parts with dangerous voltage levels under normal operating conditions.
The device must be protected from water and dust depending on the specific application and only be accessible using special tools.
(except for the front panel).
The device is ideally suited for use on household appliances and/or similar refrigeration equipment and has been tested with regard to
safety in accordance with the European harmonized reference standards.
It is classified as follows:
• for its construction, as an automatic electronic control device to be independently mounted;
• for its automatic operating features, as a 1 B-type operated control type device;
• as a Class A device in relation to the category and structure of the software.
UNPERMITTED USE
The use of the unit for applications other than those described is forbidden.
It should be noted that the relay contacts supplied with the device are functional and therefore exposed to potential faults. Any pro-
tection devices required to comply with product requirements or dictated by common sense due to obvious safety reasons should be
installed externally.