9 - EN 

EWRC 300/500 NT

English

PARA.   DESCRIPTION

U.M.

RANGE

DEFAULT

H23

Configuration of digital output 3 (OUT 3). 

num

0 ... 13

3

0

 = disabled

1

 = compressor

2

 = defrost 1 

3

 = Evaporator fans

4

 = alarm

5

 = AUX

6

 = Stand-by   

7

 = light

8

 = Buzzer output

9

 = defrost 2

10

 = compressor 2

11

 = frame heater

12

 = Condenser fans

13

 = Compressor Pump Down

H42

Evaporator probe (Pb2) present

(0) = not present

(1) = present

num

n/y

y

rEL

Firmware version release (e.g. 1,2,...). Read only. See Technical Support.

/

/

/

tAb

Map code. Read only. See Technical Support.

/

/

/

COPY CARD parameters (FPr)

UL

Upload. Transfer of programming parameters from instrument to Copy Card

/

/

/

dL

Download. Transfer of programming parameters from Copy Card to instrument

/

/

/

Fr

Formatting. To erase data on Copy Card.

IMPORTANT: If parameter “Fr” is used, the data entered will be permanently lost. This 

operation cannot be reversed.

/

/

/

THE INSTRUMENT IS USED TO EDIT OTHER PARAMETERS PRESENT IN THE 

INSTALLER LEVEL (inS) 

How to edit the installer level parameters 

Procedure applies only to more advanced applications. In this case the parameters are arranged in fold-
ers (Compressor / Defrost / Fans etc)
1) Press and hold the SET key for 3 seconds until the display shows PAr / USr
2) Use UP & DOWN to select the parameter section 

inS

3) Press and release the SET key once more. The display will show the first folder
4)  Press and release the SET key once more. The upper display will show the first parameter in the folder, 

the lower display will indicate the current parameter value

5) Using the UP & DOWN keys, find the parameter that you wish to modify
The procedure proceeds in a similar manner to that described for the User parameters (points 4-7)

OPERATION IN DEFAULT CONFIGURATION

The instrument is configured for negative cold. For positive cold, disable the evaporator probe Pb2 (set 

H42

=n) and set relay OUT3 (parameter 

H23

=6) to prevent continuous ventilation.

COMPRESSOR

The compressor is active if the cold room temperature detected by Pb1 exceeds the value of SEt + differ-
ential 

diF

. The compressor stops if the cold room temperature detected by Pb1 falls below the SEt value. 

The instrument includes compressor on/off protection*

DEFROST

Defrost is by means of electric heaters (parameter 

dty

 = 0) and the time counter is always active with the 

instrument switched on (

dCt

=1).

Manual defrost

Manual defrost is activated by pressing and holding the ESC key (A).
If conditions for defrosting are not present, (e.g. the evaporator probe temperature is higher than the 
defrost end temperature) or the parameter 

OdO≠0

, the display will blink three times to indicate that the 

operation will not be performed.

Default Defrost settings

dit

 = 6 hours. interval between 2 defrost cycles

dSt

 = 6.0 °C. defrosting end temperature set by Pb2.

The Defrost cycle may terminate due to timeout based on the parameter 

dEt

 (default 30 min).

EVAPORATOR FANS

Relay OUT3 is configured as fans relay and is activated in the required cases, according to delays and 
parameter settings*

Содержание EWRC 300 NT Series

Страница 1: ...EWRC 300 500 NT Controllers for static and ventilated cold rooms English QUICK START ...

Страница 2: ...s if function active Display alarms if active Functions Menu Info System LOC keypad lock rHC reset HACCP alarms rSE active Set reduced rPA Pressure switch rEd disable HACCP SET 18 9 rtc 18 55 Pb1 20 6 set time and date display probe value display probe value modify SetPoint value confirm with 1 sec 1 sec 1 sec 3 sec 3 sec function ON OFF Pb2 20 6 inS USr see manual diF 2 0 CPr modify value confirm...

Страница 3: ...d probe Pb3 Not configured To switch between NTC PTC probe types use parameter H00 SWITCH OFF AND RESTART THE INSTRUMENT after making the change Digital Inputs default settings DI1 Door switch DI2 not configured DI3 not configured Serial ports TTL for connection to UNICARD Copy Card MFK TTL for connection to TelevisSystem RS485 available ONLY with optional Plugin module for connection to TelevisSy...

Страница 4: ...as shown above Apply a slight pressure with your thumbs on top to release the side flaps Simultaneously with the index finger gently pull the door toward you In versions provided with the miniature circuit breaker the installer must connect it to the power supply of the electronic board through the wiring harness included in the packaging The wiring diagram is shown in the figure below In versions...

Страница 5: ...ngON EnergysavingOFF 3 NIGHT DAY amber Night DayON Night DayOFF 4 HACCP amber HACCPmenu 5 DEEPCOOLING DCC amber DripcoolingcycleON DripcoolingcycleOFF 6 PUMPDOWN amber CompressorPumpDownON CompressorPumpDownOFF 9 COMPRESSOR amber CompressorON delay CompressorOFF 10 DEFROST1 amber defrost coildrainage Nodefrost 11 EVAPORATORFANS amber FansON forcedventilation FansOFF 12 DEFROST2 amber defrost coild...

Страница 6: ...d are described in this document in the section Parameters Table 1 Press and hold the SET key for 3 seconds until the display shows PAr USr 2 Press and release the SET key once more The upper display will show the first parameter the lower display will indicate the current parameter value 3 Using the UP DOWN keys find the parameter that you wish to modify 4 Press and release the SET key once more ...

Страница 7: ...n delay The parameter indicates that a protection is active on the general compressor relay actuations At least the indicated time must elapse between the request and the actual activation of the compressor relay sec 0 255 2 dOF Delay time after power off the delay time indicated must elapse between deactivation of the compressor relay and the next power on min 0 255 0 dbi Delay time between power...

Страница 8: ... is switched on following a power failure This parameter refers to high low temperature alarms LAL and HAL only hours 0 10 3 dAO Temperature alarm override time after defrost min 0 250 60 tAO Delay preceding indication of temperature alarm This parameter refers to high low temperature alarms LAL and HAL only min 0 250 0 DISPLAY parameters diS LOC LOCk Setpoint edit lock The parameter programming m...

Страница 9: ...ll show the first parameter in the folder the lower display will indicate the current parameter value 5 Using the UP DOWN keys find the parameter that you wish to modify The procedure proceeds in a similar manner to that described for the User parameters points 4 7 OPERATION IN DEFAULT CONFIGURATION The instrument is configured for negative cold For positive cold disable the evaporator probe Pb2 s...

Страница 10: ...o indicate system alarms see Alarms Table HACP to indicate HACCP alarms see HACCP alarms 2 Using the UP DOWN keys find the type of alarm that you want to check System alarms The upper display will show the label ALr the lower display will indicate the alarm code see Alarms Table Using the UP DOWN key scroll the other alarms Press the ESC key to return to the previous alarm code press the ESC key s...

Страница 11: ...1 H12 Depends on delay set by parameter tdO Recording of label OPd in folder ALr Regulator locked see para dOA PEA Close door Depends on delay set by parameter OAO E10 Models with clock only Clock alarm clock faulty or battery low Functions associated with clock not present Contact EliwellTechnical Support ALL ALARMS Alarm icon permanently alight Buzzer if present and alarm relay OUT5 activated ex...

Страница 12: ...tted well and lie flush so that they do not interfere with the compression of the seal Type of action 1 B Pollution class 2 Material class IIIa Over voltage category II Nominal pulse voltage 2500 V Operating temperature 5 50 C Power supply 230 Vac 10 50 60 Hz Power consumption 11 VA max Miniature Circuit Breaker EWRC 500 BREAKER version only 230 Vac Icn 4500 A Bipolar 2P for wires up to 10 mm2 Rat...

Страница 13: ...tal Inputs 2 3 digital inputs no voltage configurable from parameter H11 H12 H13 Relay outputs EWRC 300 NT version OUT1 output SPST 2 HP 12 12 A 250 Vac OUT2 output SPST 1 HP 8 8 A 250 Vac OUT3 output SPST 1 2 HP 8 4 A 250 Vac common line max 18 A EWRC 500 NT version OUT1 output SPST 2 HP 12 12 A 250 Vac OUT2 output SPST 1 HP 8 8 A 250 Vac OUT3 output SPST 1 2 HP 8 4 A 250 Vac OUT4 output SPST 1 H...

Страница 14: ...the controller RESPONSIBILITY AND RESIDUAL RISKS Eliwell Controls srl declines any liability for damage due to installation uses other than those expressly specified and in particular failure to comply with the safety requirements of established standards and or instructions specified in this document use on panels that do not provide adequate protection against electric shock water or dust when m...

Страница 15: ...CUT OUT 110 6 5 29 60 25 45 Lower Side UM mm SCALE 1 1 when printed A5 format ...

Страница 16: ... 0437 986 111 www eliwell com Technical Customer Support T 39 0437 986 300 E techsuppeliwell schneider electric com Sales T 39 0437 986 100 Italy T 39 0437 986 200 other countries E saleseliwell schneider electric com 9IS54389 EN rel 10 16 Eliwell Controls s r l 2014 2016 All rights reserved ...

Отзывы: