Scenario 1: Hipot Test with Emergency LED Driver and
AC Driver

             Caution: 

PLEASE FOLLOW THE WIRING DIAGRAM BEFORE 
DOING HIPOT TEST, OTHERWISE IT MIGHT CAUSE 
DAMAGE TO THE EMERGENCY DRIVER OR AC DRIVER.

HIPOT TEST

TECHNICAL SPECIFICATIONS

Ground

Driver must be grounded

Scenario 2: Hipot Test with Emergency LED Driver
without AC Driver

Ground

Driver must be grounded

LED Emergency

Pack

LED Indicator

& Test Switch

Yellow/Black

White

Brown

Yellow

Red
Blue

Neutral

Battery 

Connector

Fig C: Short  two input wires White, 

Yellow/Black and open Black wire

Line

Ht terminal

1.5KV

5mA/1 sec

Test Voltage

Leakage Current

PAGE 4 OF 4

O.R.-Revision C: 2/24/21

323-888-1973

[email protected]

www.iuseelite.com

There are two di

erent scenarios for performing hipot test;

1) With an AC driver
2) Without an AC driver
Wiring diagrams for both scenarios are provided as below. Please
follow the wiring diagram before performing hipot testing. The
recommended setting is 1.5KV, 5mA/1sec

0-10V

Dimmer

1

10V

Gray

LED Emergency

Pack

AC LED Driver

LED Indicator

& Test Switch

Yellow/Black

White

White

Black

Red

Blue

Brown

Yellow

Red
Blue

Wall

Switch

Neutral

Battery 

Connector

Violet

Fig B: Short all three input wires White, Yellow/Black, 

Black, and cap o

 Black from Emergency driver 

Optional

ON

Line

Ht terminal

1.5KV

5mA/1 sec

Test Voltage

Leakage Current

In Figure A, we short all the input wires White, Yellow/Black and Black 
wires together. Also, the user must ensure the optional wall switch is 
“ON”. It is safe to begin hipot testing .

Ground

Driver must be grounded

In Figure B, all three input wires White, Yellow/Black and Black wire 
from AC driver are shorted together. Also the user must ensure the 
optional wall switch is “ON”. The black wire from Emergency LED driver
should also be "capped o

" (left open) It is safe to begin hipot testing.

In Figure C, two input wires White and Yellow/Black are shorted, and 
the Black wire is "capped o

" (left open). It is safe to begin hipot 

testing.

10W Model 

20W Model

Input Voltage 

120-277VAC 

120-277VAC 

Input Current 

60mA 

Input Power 

10W Max 

20W Max 

Frequency 

50/60Hz 

50/60Hz 

Output Voltage 

15-55VDC 

15-55VDC 

Output Current 

190mA 

380mA 

Ambient Temperature 

0°C - 55°C 

0°C - 55°C 

Max Case Temperature 

66°C 

66°C 

Ba

ery Type 

LiFePO4 

LiFePO4 

Installa

on Type 

Factory or Field 

Factory or Field 

Min Dura

on Time 

90min 

90min 

Recharge Time 

24Hrs 

Ba

ery Voltage 

6.4VDC 

Ba

ery Charge Current 

185mA 

0-10V

Dimmer

1

10V

Gray

LED Emergency

Pack

AC LED Driver

LED Indicator

& Test Switch

Yellow/Black

White

White

Black

Red

Blue

Brown

Yellow

Red
Blue

Wall

Switch

Neutral

Battery 

Connector

Violet

Fig A: Short all three input wires White, 

Yellow/Black and Black together 

Optional

ON

Line

Ht terminal

1.5KV

5mA/1 sec

Test Voltage

Leakage Current

70mA

48Hrs

   9.6VDC

  210mA

Отзывы: