Elite EMG-LED-G2-10W Скачать руководство пользователя страница 1

EMERGENCY BACKUP

INSTRUCTIONS

EMG-LED-G2-10W/EMG-LED-G2-10W-FLEX
EMG-LED-G2-10W-LP/EMG-LED-G2-10W-FLEX-CP
EMG-LED-G2-10W-INTG-FLEX/EMG-LED-G2-20W-INTG-FLEX
EMG-LED-G2-20W-EMG-LED-G2-20W-FLEX

1.

2.

3.

4.

This product is intended for use with an emergency LED lighting load and
supplies nominal of power and a maximum voltage in emergency mode
for a minimum of 90 minutes.

14.

15.

11.

7.

IMPORTANT SAFEGUARDS

16.

Do not a ttempt to service the battery. It is a sealed no maintenance 
battery is used that is not 

eld replaceable. Contact the manufacturer 

for information on service.

17.

Servicing should be performed by quali

ed service personnel only.

             Note: 

             Make sure the necessary branch circuit wiring is available. 
             An uns witched source of power is required. The emergency 
driver must be fed from the same branch circuit as the AC driver.

             Caution: 

             

DO NOT JOIN BATTERY CONNECTOR OR ACTIVE 

              BATTERY SWITCH UNTIL INSTALLATION IS COMPLETE 
              AND AC POWER IS SUPPLIED TO THE EMERGENCY DRIVER

.

SAFETY US-CA

EMER. LIGHT & 

POWER EQ

.

E359672

5LG2

 

PAGE 1 OF 4

O.R.-Revision C: 2/24/21

323-888-1973

[email protected]

www.iuseelite.com

Do not join battery connector or turn "ON" the battery switch until 
installation is complete and AC power is supplied to the emergency
driver.

An unswitched AC power source is required (115-277 VAC, 50/60 Hz) to 
power these units

This product ’s chassis must be grounded.

This device complies with part 15 of the FCC Rules. Operations is suitable 
to the following two conditions: (1) This device may not cause harmful 
interference, and (2) This device must accept any interference that may 
cause undesired operation.

 

To reduce the risk of electric shock, disconnect both normal and 
emergency power supplies and place the battery switch in the "OFF" 
or disconnect the battery connector of the emergency driver before
servicing.

Do not use this product for anything other than it’s intended use.

Make certain all connectors are in accordance with the National 
Electrical Codes or Canadian Electrical Cose and any local regulations.

1.

2.

Verify that the forward voltage of the luminaire s LED array is within the
limits of this emergency LED driver. The forward voltage of the LED array
is commonly designated as Vf and should be found on the luminaire, in
the luminaire speci

cations, or imprinted directly on the LED arrays. If

multiple LED arrays are to be driven, verify that the total forward voltage
is within the limits of this product. Using a voltage meter, it may be
possible to directly measure the voltage across the LED arrays when
operating from the AC driver.

Ensure the LED load's rated power is greater than or equal to the 
power output of this emergency LED driver. This is to ensure that this 
emergency product will not produce more power than the LED load
can handle. Thus ensuring that the LED load will not be damaged 
when the sy tem is in the emergency mode.

3.

Ensure the output current of th e LED driver does not exceed 5 Amps.
This is the current into the red/ blue output wire.

CLASS 2

OUTPUT

5.

This product is suitable for use in damp locations where the ambient 
temperature is 0°C minimum, to 60°C maximum. This product is also 
suitable for installation in sealed and gasleted 

xture. This product is 

not suitable for heated air outlets and wet or hazardous locations. For 
the 10W models,m aximum allowable case temp is 66°C For the 20W 
models, maximum allowable case temp is 70 °C. See the section of 
this document for TC measurement location.

6.

This product contains a rechargeable LiFePO4 battery. The battery 
must be recycled or disposed of properly.

8.

This emergency LED driver is suitable for both factory or 

eld 

installation. For 

eld installation, please see the instructions section.

9.

Do not install near gas or electric heaters.

10.

The use of accessory equipment is not recommended by the 
manufacturer may cause an unsafe condition.

12.

Equipment should be mounted in locations and at heights where it will 
not be subjected to tampering by unauthorized personnel.

13.

For Canadian applications, the output terminal should be in compliance 
with the accessibility requirement of the Canadian Electric Code.

This product is suitable for 

eld installation with suitable LED loads. 

There are Three (3)  checks to determine if your luminaire is eligible 
for 

eld installation.

Отзывы: