background image

 

 

PARALLEL CONNECTION 
 
 

For  larger  pools,  it  may  be  necessary  to  connect 
two  heat  pumps  in  parallel.  Make  sure  you  install 
them at least 2 feet apart. 
1, 2 and 3: optional valves 
4: filter 
5: water pump 

 
 
 
 
 

 

 

 
 

CONNECTION TO ELECTRICAL POWER 

To ensure your safety and the proper functioning of the device, the electrical connections must be 
performed by a qualified electrician according to national codes, provincial and local regulations. 
 
A circuit breaker must be installed close to the heat pump, in an accessible location. 
 
Never open the electrical box without shutting off the power to all sources used for the operation of the 
heat pump. If your heat pump has a pool pump control option, remember to close the circuit breaker to 
this pump. 
 
The spec sheet for the heat pump contains all the requirements for voltage and amps. 
If the power cord is damaged, it must be replaced by a qualified electrician. 
 
 

 

 

WARNING 

When you shut off the water to one of the heat pumps, the water flow that previously 
went through the heat pump is redistributed to the other heat pumps. Valves must be 
adjusted to obtain the prescribed water pressures (see page 7).

 

Содержание 100

Страница 1: ... 55 65 85 100 115 130 IMPORTANT It is important to register your product with us on our web site This will help us find your warranty when you place a service call If we cannot find your warranty registration a proof of purchase will be necessary www ttifab com warranty php ...

Страница 2: ...or removing any Elite equipment make sure that all breakers covering the pool area have been turned off A clearly identified breaker must be installed in order to be able to interrupt power to the heat pump in case of an emergency Never open the electrical box without having shut off all power sources to the heat pump beforehand If your heat pump is equipped with a water pump control option don t ...

Страница 3: ...ned on the rating plate Elite heat pumps have a 240V 1 phase voltage Make sure you have the appropriate electrical connections Make sure that there is no watering or sprinkler system near or aimed at the water heater Most water sprinkling systems are connected to wells whose water contains minerals Sulphur and other aggressive contaminants These contaminants may promote corrosion and affect the ef...

Страница 4: ...ections Minimum and maximum water flows IV CHLORINATORS BROMINATORS AND OTHERS P 8 9 Basic connections inline chlorinator or brominator Salt chlorinator Pressurized chlorinator or brominator Parallel connection V CONNECTION TO ELECTRICAL POWER P 9 VI MAINTENANCE P 10 Cleaning Winterizing Seasonal restart Water bypass VII REGULATOR P 11 12 VIII ALARM CODES P 13 IX TROUBLE SHOOTING P 14 X QUESTIONS ...

Страница 5: ...possible to achieve yields of up to 600 or 700 under optimum conditions or a COP of between 6 and 7 In other words for every kilowatt that your heat pump uses it transfers up to 6 or 7 kilowatts between the air and the water in your pool This compares favorably with the 80 to 95 yield of a traditional gas oil or electric pool water heater However it is true that the performance of traditional pool...

Страница 6: ...il 60 cm 2 feet 2 in front of all other surfaces 35 cm 14 inches 3 in front of the fan 120 cm 4 feet 4 in front of the service panel 60 cm 2 feet Objects should be placed as far away as possible from the area where air is evacuated OTHER RECOMMENDATIONS You should not install the device below a roof so that your heat pump becomes buried under snow or receives too much water if the roof is not fitt...

Страница 7: ...ndenser An adjustable automatic bypass valve must be installed when a water pump of 2 HP or more is used to circulate the pool water Your water pump must be able to supply each heat pump with a water flow within the limits listed below MODEL MINIMUM IDEAL MAXIMUM Elite 50 65 57 l m 15 GPM US 170 l m 45 GPM US 170 l m 45 GPM US Elite 85 100 115 130 77 l m 20 GPM US 170 l m 45 GPM US 170 l m 45 GPM ...

Страница 8: ...lation is not compliant to this rule SALT CHLORINATORS Salt chlorinators are made to be installed as inline chlorinators Therefore they must be installed as prescribed in the section above inline chlorinator or brominator PRESSURIZED CHLORINATOR OR BROMINATOR Pressurized chlorinators or brominators start by using a small quantity of water as it exits the filter then add chemicals and forward this ...

Страница 9: ...lose to the heat pump in an accessible location Never open the electrical box without shutting off the power to all sources used for the operation of the heat pump If your heat pump has a pool pump control option remember to close the circuit breaker to this pump The spec sheet for the heat pump contains all the requirements for voltage and amps If the power cord is damaged it must be replaced by ...

Страница 10: ...nse the condenser with tap water and drain the system with air pressure or vacuum 5 Cover the unit with a waterproof drop cloth if left outside all winter SEASONAL RESTART Before restarting your pool heat pump you must 1 Check and adjust the quality of the pool water 2 Make sure the breaker for the heat pump is turned off 3 Install the heat pump on a level surface and connect all plumbing 4 Clean ...

Страница 11: ...hine is on 2 Water temperature setting a Press MODE key can switch HEAT circulating mode b Available no matter the machine is on or off Press HEAT light up c Press the key or to set water temperature The controller indicates flashing temp Press or to adjust to your desired water temp d 5 seconds later the controller display will back to the normal mode ...

Страница 12: ... to set minute B Use or to adjust After adjusting press and water temperature will been seen 30 seconds later the controller display will be back to the normal mode C Press to set timer off When the indicator light is on and the time is flashing press again to set hour Use or to adjust before flashing stop press to set minute Use or to adjust After adjusting press and water temperature will been s...

Страница 13: ...tection E 4 Over current 3 phase machine E 6 Compressor exhaust overload protection PP 1 Pool SPA heater sensor failure PP 2 Exhaust sensor failure PP 3 Coil pipe sensor failure PP 4 Intake pipe sensor failure PP 5 Air temp sensor failure PP 7 When the temperature 32 auto stop protection not Failure ...

Страница 14: ...del or use more than one heat pump There is a lot of water under the device Normal runoff due to condensation Abnormal water leak No action required install a drain if necessary To determine whether this is a leak turn off the device until all condensation runoff has gone See if there is still water after 24 to 48 hours There is frost on the evaporator Outdoor temperature is cold Compressor works ...

Страница 15: ...rmometer is often offset with respect to the graduations marked on the casing The thermometer displays temperatures higher or lower than the actual temperature of the water To measure the water temperature you can use an oral thermometer on which the graduations are more precise When pools have a bottom drain it is also possible that the pool heat pump displays a temperature of 1 to 2 degrees lowe...

Страница 16: ...16 TTI FABRICATION Inc 684 Place Trans Canada Longueuil QC J4G 1P1 Canada www ttifab com www ttifab com ...

Отзывы: