Troubleshooting: Alarm Messages
This section covers only the common and likely causes of alarm messages and actions
that should be taken by the operator.
UNIDRIVE alarms can be interpreted using the
Telemetry Panel
(See Chapter 5),
Elife Diagnostic Display
or can be read through the
CanOpen
®
Protocol also.
Note
In Advanced Tab in Telemetry Panel software is present a
Reset Alarms
button
that allows you to reset all running alarms.
After the resolution of the problem, UNIDRIVE might need to be restarted.
Configuration Alarm
DESCRIPTION
This error appears when:
•
No
configuration
(Standalone, CAN Network, PLC, EV, RS232) is selected.
•
Set
pole number
is different from allowed values.
•
The internal memory of UNIDRIVE has never been programmed.
UNIDRIVE BEHAVIOUR
After switch on, drive won’t enable power relay and three-phase
bridge.
POSSIBLE TROUBLESHOOTING ISSUE
1.
Check if a configuration is selected in the
Configuration
list (See Section
2.
If the other programmable parameters are null, it also needs to download
parameters from motor configuration file (See Section 3.3).
3.
Check if the
pole number
value is correct (See Section 3.4.5).