Disturbances, Maintenance, Cleaning
- 73 -
14
Disturbances, Maintenance, Cleaning
This chapter describes possible causes for disturbances and measures for their removal. In case of increased disturbances, please follow the
measures for fault clearance in chapter 14.1. In case of disturbances that cannot be eliminated by following the advice and the fault clear-
ance measures given here, please contact the manufacturer (see second page).
14.1
Fault Clearance
CAUTION!
The device, the connection line and the signal cable must not be installed next to sources of interference that emit
strong inductive or capacitive interference or strong electrostatic fields.
External perturbations can be avoided thorough suitable cable routing.
The screen of the signal output cable should only be connected to the following circuit on one side. The screens
should not be grounded on both sides. Signal cables always have to be routed separately from the load power line.
A safety distance of at least 0.5 m has to be kept from inductive and capacitive sources of interference such as con-
tactors, relays, motors, switching power supplies, clocked controllers etc.!
If interferences occur in spite of all the items stated above being observed, please proceed as follows:
1.
Installation of RC-circuits via contactor coils of AC-contactors (e.g. 0.1 µF / 100
Ω
)
2.
Installation of recovery diodes via DC-inductors
3.
Installation of RC-circuits via the different motor phases (in the terminal box of the motor)
4.
Do not connect protective earth and ground
5.
Connect a mains filter ahead of the external power pack