Disturbances, Maintenance, Cleaning 

- 18 - 

7

 

Disturbances, Maintenance, Cleaning 

This chapter describes possible causes for disturbances and measures for their removal. In case of increased disturbances, please follow the 

measures for fault clearance in chapter

 

 7.1. 

In case of disturbances that cannot be eliminated by following the advice and the fault clearance measures given here, please contact the 

manufacturer (see second page). 

7.1

 

Fault Clearance 

 

CAUTION! 

The device, the connection line and the signal cable must not be installed next to sources of interference that emit 

strong inductive or capacitive interference or strong electrostatic fields. 

External perturbations can be avoided thorough suitable cable routing.

 

 

 

The screen of the signal output cable should only be connected to the following circuit on one side. The screens 

should not be grounded on both sides. Signal cables always have to be routed separately from the load power line. 

A safety distance of at least 0,5 m has to be kept from inductive and capacitive sources of interference such as con-

tactors, relays, motors, switching power supplies, clocked controllers etc! 

If interferences occur in spite of all the items stated above being observed, please proceed as follows: 

1.

 

Installation of RC-circuits via contactor coils of AC-contactors (e.g. 0,1 µF / 100 

2.

 

Installation of recovery diodes via DC-inductors 

3.

 

Installation of RC-circuits via the different motor phases (in the terminal box of the motor) 

4.

 

Do not connect protective earth and ground 

5.

 

Connect a mains filter ahead of the external power pack

 

7.2

 

Re-start after Fault Clearance 

After the fault clearance: 

1.

 

Reset the emergency stop mechanism if necessary 

2.

 

Reset the error report at the super-ordinate system if necessary. 

3.

 

Ensure that there are no persons in the danger area. 

4.

 

Follow the instructions from chapter

 

 5. 

 

WARNING! 

Danger of injury through non-conventional fault clearance! 

Non-conventional fault clearance can lead to severe injuries and damage of property. 

Therefore: 

 

Any work to clear the faults may only be performed by sufficiently qualified staff 

 

Arrange enough space before starting the works 

 

Make sure that the mounting area is clean and tidy. Loose components and tools are sources of accidents. 

If components need to be replaced: 

 

Pay attention to a correct installation of the spare parts. 

 

Reinstall all the fixing elements properly 

 

Before turning on the device, ensure that all covers and safety equipment is installed correctly and functions 

properly 

 

 

Содержание EMAX-RO Series

Страница 1: ...ve applications Distance monitoring by LED High resolution 16000 steps per turn Additional incremental signals for highly dynamic drives Diverse interfaces available Standard SSI or CANopen On request...

Страница 2: ...Benz Str 1 D 78239 Rielasingen Technical Support 49 0 7731 9339 0 49 0 7731 2 13 11 info elgo de Document No 799000708 Document Name EMAX RO 00 MA E_46 17 Document Revision Rev 3 Issue Date 2016 11 1...

Страница 3: ...Functional principle 7 4 Technical Data 8 4 1 Identification 8 4 2 Dimensions of Sensor 8 4 3 Dimensions of Magnetic Ring 9 4 4 Technical Data Sensor 10 4 5 Technical Data Magnetic Ring 10 5 Installa...

Страница 4: ...to avoid accidents damage and injuries Warning notes DANGER This symbol in connection with the signal word Danger indicates an immediate danger for the life and health of persons Failure to heed thes...

Страница 5: ...before using the device Observe the installation instructions Only start up the device if you have understood the operating manual The operating company is obliged to take appropriate safety measure T...

Страница 6: ...d Loading CAUTION Transport the package box palette etc professionally Do not throw hit or fold it 2 9 Handling of Packaging Material Notes for proper disposal 2 4 2 10 Inspection of Transport Check t...

Страница 7: ...signal 1Vss Direct measurement on engine shaft or axle possible 3 1 Functional principle A Hall sensor and a magneto resistive impedance measuring bridge are guided over a two track magnetic tape wit...

Страница 8: ...r and gives the exact type designation order reference see chapter type designation with the corresponding part number Furthermore the type label contains a unique traceable device number When corresp...

Страница 9: ...etic ring dimensions without protection ring Usage up to maximum 1000 rpm 4 3 2 Dimensions of Magnetic Ring with Protection Ring Figure 4 Magnetic ring dimensions with protection ring Usage up to maxi...

Страница 10: ...5 m standard length accessory other on request Electrical Data Power supply 10 30 VDC Ripple 5 Current consumption max 150 mA Interfaces SSI or CANopen DS406 on request CAN BASIC ELGO CN0 RS422 addre...

Страница 11: ...electrostatic fields CAUTION The electrical connections must be made by suitably qualified personnel in accordance with local regulations The device may be designed for switchboard mounting During wo...

Страница 12: ...Magnetic ring Table 1 Installing Tolerances Tolerances Ride height Sensor Magnetic Ring 0 5 mm max 1 0 mm without protection ring resp max 0 45 mm with protection ring Roll Pitch The max distance of 1...

Страница 13: ...o point an offset should to be deposited at the controller side NOTE The offset should be arranged at any change from measurement system sensor head or magnetic ring 5 2 4 Activation of the device The...

Страница 14: ...le for adhesive mounting Figure 7 Magnetic ring example for adhesive mounting 5 3 2 Example for screw mounting Figure 8 Magnetic ring example for screw mounting 30 h6 Steel shaft with h6 fit EMAX RO m...

Страница 15: ...C 3 green CLK 4 yellow CLK 5 grey DATA 6 pink DATA 7 blue COS or B 8 red COS or B 9 black SIN or A 10 violet SIN or A 11 NC NC 12 NC NC Table 3 Pin Assignment CA0 optionally with incremental signals T...

Страница 16: ...lue error recognition in evaluation Some encoders contain a Power Failure Bit PFB With EMAX RO the PFB is always LOW Figure 9SSI Interface 6 2 2 Interface CANopen option CA0 As standard the EMAX RO me...

Страница 17: ...al TTL HTL 6 2 4 Sine Cosine Incremental Signal Option SC50 Sine Cosine signals with 1 Vss are available as an option push pull output stage short circuit proof Parameter Description min typ max unit...

Страница 18: ...s occur in spite of all the items stated above being observed please proceed as follows 1 Installation of RC circuits via contactor coils of AC contactors e g 0 1 F 100 2 Installation of recovery diod...

Страница 19: ...ventional maintenance Non conventional maintenance can lead to severe injuries and damage of property Therefore Maintenance works may only be completed by staff that has been authorized and trained by...

Страница 20: ...th CAN 250k 250000 Bit s with CAN 500k 500000 Bit s with CAN 1MHz 1000000 Bit s with CAN Options F device address 0 F standard configuration address 0 Options standard version always with 12 pole M12...

Страница 21: ...n suitable screen available 8 3 Type Designation Magnetic Ring Figure 14 Type designation of Magnetic Ring NOTE When ordering please use the here described ordering code Type Designation Options that...

Страница 22: ...Type Designation 22 Notes...

Страница 23: ...Tolerances 12 Interface CANopen option CA0 16 Interfaces 16 Interfaces and Assignment 15 Magnetic Ring mounting suggestions 14 Maintenance 18 19 Mounting direction 12 Offset 13 Operating area 11 Opera...

Страница 24: ...EMAX RO 00 MA E_46 17 Subject to change 2017 ELGO Electronic GmbH Co KG ELGO Electronic GmbH Co KG Measuring Positioning Control Carl Benz Str 1 D 78239 Rielasingen Fon 49 0 7731 9339 0 Fax 49 0 7731...

Отзывы: