SINUS PENTA
PENTA MARINE
IRIS BLUE
STO FUNCTION
APPLICATION MANUAL
26/
27
8. STO TECHNICAL DATA
8.1. STO Data Related to Safety Standards
Data related to safety standards IEC 61508, EN 61800-5-2, EN/ISO 13849-1 are listed below.
Data apply to all sizes of inverter of Sinus Penta, Iris Blue and Penta Marine line.
IEC 61508
EN/ISO 13849
SIL
PFH
G
HFT
SFF
DC
Category
PL
CCF
3
2.383 x 10
-9
1
98.43 %
78.51 %
3
d
75
Maximum reaction time to ensure the safe state on demand:
1.86 ms
Maximum reaction time to ensure the safe state on fault detection:
8.60 ms