background image

Displaying Current Temperature and Temperature Setting

Press the “Set” button to alternately display the current temperature and 

the programmed temperature. The temperature indicator light blinks when 

the programmed temperature is displayed.

Selecting Temperature Setting

Hold the “Set” button for 3 seconds. The programmed temperature will 

appear on the display. Use the “Up” and “Down” arrow buttons to adjust 

the setting. Press the “Set” button again or wait for 8 seconds to accept the 

setting.

Correcting Temperature Error

If the actual water temperature is different from the current temperature 

displayed by the chiller, correct the error by holding the “Up” and “Down” 

arrow buttons simultaneously for 6 seconds until “0” appears on the screen. 

Use the “Up” and “Down” arrow buttons to select the difference between 

the displayed temperature and the actual water temperature. Use the “Up” 

and “Down” arrow buttons to adjust the displayed temperature. 

Note:

 Use 

this function only if necessary.

Compressor Operation

The compressor will begin operating when the water temperature reaches 1.8°F above the temperature setting. The compres-

sor will stop operating automatically when the water temperature is at or below the temperature setting.

To prevent damage to the compressor, the unit enters protection mode when the compressor stops and will not restart the com-

pressor for 3 minutes. The operation indicator light illuminates when the compressor is operating and blinks when the unit is in 

protection mode. 

Replacing the Fuse

Disconnect the unit from the power source. Unscrew the panel on the side of the unit where the power cord attaches. Pull out 

the fuse and replace it with the included replacement fuse. Replace the panel and reconnect the unit to the power source.

Cleaning and Storage

•  The unit should be cleaned every 1-2 months to maintain optimal performance. Always disconnect the unit from the power    

  source before cleaning it.

•  Rinse debris from the water inlet and outlet fittings.

•  Clean the front of the unit using a vacuum cleaner or brush.

•  To clean the air filter, loosen the screw on the front cover panel and remove 

  the panel. Loosen the screws holding the air filter, then remove the filter 

  and clean it using a vacuum cleaner or brush. Replace the filter and front 

  cover panel.

•  To store the unit when not in use, remove the inlet and outlet fittings. Tilt the unit to the side to allow the water to drain.  

 

  Clean all parts with a soft dry cloth. Cover the unit and store it in a dry location.

Troubleshooting

The unit isn’t operating and the display isn’t illuminated.

If the power cord is plugged in and the unit is turned on, the fuse may need to be replaced. See the “Replacing the Fuse” sec-

tion.

The unit turns on or off unexpectedly.

Ensure the unit is connected to a power source with the correct voltage and frequency. If the unit has recently been turned off, 

the compressor will not restart for 3 minutes.

The unit is not cooling the water sufficiently or at all.

Ensure the temperature setting is lower than the current water temperature. Clean the air inlet and outlet if necessary. If the 

problem persists, the water in the reservoir may need to be reduced, the fan may need to be replaced, or the refrigerant may 

be low. All repairs should be performed by a licensed professional.

The unit is vibrating or operating noisily.

Ensure the unit is installed on a stable and level horizontal surface.

Decrease Temperature

Increase Temperature

Setting Temperature

Temperature Indicator

Temperature Display

Operation Indicator

Operation Panel

Содержание EHC200

Страница 1: ...warranty EHC200 Input Voltage 120V Amperage 2 2A Wattage 170W BTU 1 130 BTU Water Capacity 13 40 gallons Recommended Pump Size 130 280 gph Flow Rate 66 5 410 gph Refrigerant R134a Compatible Tubing 1 2 or 3 4 ID EHC210 Input Voltage 120V Amperage 3A Wattage 310W BTU 2 940 BTU Water Capacity 26 80 gallons Recommended Pump Size 250 600 gph Flow Rate 264 660 gph Refrigerant R134a Compatible Tubing 3 ...

Страница 2: ...secure the tubing to the fittings 4 Before turning the unit on turn on the pump Ensure none of the tubing connections leak and water is circulating from the pump to the chiller 5 Plug the unit into a grounded outlet and turn the power switch to ON Read all instructions carefully before operating the unit Do not allow the unit s electrical components to be exposed to water If the electrical compone...

Страница 3: ...he included replacement fuse Replace the panel and reconnect the unit to the power source Cleaning and Storage The unit should be cleaned every 1 2 months to maintain optimal performance Always disconnect the unit from the power source before cleaning it Rinse debris from the water inlet and outlet fittings Clean the front of the unit using a vacuum cleaner or brush To clean the air filter loosen ...

Страница 4: ...UT LIMITATION MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE Elemental H2O Chiller Warranty Is Void If NOT ACCOMPANIED BY THE ORIGINAL PROOF OF PURCHASE ELEMENTAL H2O CHILLER HAS BEEN USED IN A NONSTANDARD WAY INCLUDING GENERAL MISUSE AND OUTDOOR USE ELEMENTAL H2O CHILLER HAS BEEN DAMAGED AS A RESULT OF ACCIDENT IMPROPER INSTALLATION ALTERATION OR FIRE FLOOD OR OTHER NATURAL DISASTER Don t f...

Отзывы: