ABMHZ Version 1+1 

Advanced User Manual

 

20 November 2007     Rev. B 

©2007, Electronic Solutions, Inc. 

page 5 of 5 

 

 

 
If the OPEN button closes the shade instead of opening it, the motor direction 
must be reversed using one of the following: 
 

1.

 

Use the reverse direction & calibrate button sequence 

2.

 

Set Configuration Parameter #2 to a 1 

3.

 

Swap motor directional wires on the motor connector. 

 
Pressing the CLOSE button should close the shade. (If it does not, fix this as 
described above)  
 
A press of either button while the shade is moving will cause the shade to stop. 

12.

 

Calibration 

Calibration is required before SET and GET will work correctly. Calibration is 
accessed by pressing and holding down both the OPEN and CLOSE buttons 
simultaneously for approximately 10 seconds, until the Motor LED turns green. 
 
While the Motor LED is green (within 10 seconds): 
 

 

Press the CLOSE button to start a calibration sequence. 

- or -   

 

Press the OPEN button to reverse the motor direction and start a calibration 
sequence. 

 
A calibration sequence consists of the shade moving between the upper and lower 
limits and stopping at the fully closed position. 
 
After the calibration sequence completes, the Motor LED turns off. 
 

 

NOTE:

 The ABMHZ is a Z-Wave enabled device and is fully compatible with any Z-Wave enabled network.  Z-Wave 

enabled devices displaying the Z-Wave logo can also be used with ESI Z-Wave enabled motor controllers such as 
ABMHZ regardless of the manufacturer.  ESI  Z-Wave enabled motor controllers can also be used in other 
manufacturer’s Z-Wave enabled networks and all listening devices act as repeaters, regardless of vendor. 

 
 
 

Содержание ABMHZ

Страница 1: ...sor Version 1 This LED will blink green on reception of a valid Z Wave command This LED will blink red if an error has occurred 3 Motor LED On power up this LED will blink RED once indicating motor processor Version 1 This LED will stay red after power up if the unit is not calibrated This LED will be green when ready for calibration please see Calibration section 4 COMMAND_CLASS_CONFIGURATION Com...

Страница 2: ...a 0 or 1 Return to factory defaults Unit uncalibrated motor direction normal tilt disabled 5 COMMAND_CLASS_BASIC Commands A BASIC_GET will return a motor position value between 0 and 99 or 255 A value of 255 means the motor is not calibrated and cannot report a valid position The Motor LED will also be red A BASIC_SET 0 will move the shade of a properly calibrated motor to the fully closed positio...

Страница 3: ...WITCH_START_LEVEL_CHANGE with parameter 1 bit 6 set causes the position value to decrease and the shade closes regardless of the calibration status The values of the Ignore Start Level bit parameter 1 bit 5 and the Start Level parameter parameter 2 are ignored However for compatibility with other Z Wave devices the Ignore Start Level bit should be set to 1 Sending a MULTILEVEL_SWITCH_STOP_LEVEL_CH...

Страница 4: ...cknowledged It is also possible to query for the results of the last test by sending a POWERLEVEL_TEST_NODE_GET Send POWERLEVEL_SET 5 60 to set node to power level 5 mid level power for 60 seconds 9 COMMAND_CLASS_MANUFACTURER_SPECIFIC Command Send MANUFACTURER_SPECIFIC_GET The return message should be 0x00 0x33 0x52 0x50 0x30 0x31 This shows the ESI product data as Manufacturer ID 0033 Product Typ...

Страница 5: ...d CLOSE buttons simultaneously for approximately 10 seconds until the Motor LED turns green While the Motor LED is green within 10 seconds Press the CLOSE button to start a calibration sequence or Press the OPEN button to reverse the motor direction and start a calibration sequence A calibration sequence consists of the shade moving between the upper and lower limits and stopping at the fully clos...

Отзывы: