4
REMOTE CONTROL INPUT:
TB 1 (located on upper board) also has provisions for 120 VAC Remote Control Signal. This
input enables the timer to be switched remotely between the 4-20 mA mode and the
continuous cycle mode.
PULSE OUTPUT:
TB 2 (located on lower board) provides a 120 VAC signal every time an output is pulsed.
This can be used to monitor timer operation or count pulses.
FEATURES:
•
120 VAC 50/60 Hz, One phase
•
One amp maximum capacity per output
•
One amp fuse protection
•
All solid state industrial quality construction
•
Illuminated Digital indication of next output to fire, and indicates timer operation.
•
Adjustable ON time 50 - 150 ms
•
Proportional OFF time, minimum of 3 sec.
•
Settable OFF time: 3-120 sec. If in Hold Off Mode.
•
Remote switching between Continuous Clean and
Δ
P control
•
Differential set point, adjustable 2 to 6 in. H
2
O
•
UL Recognized to US and Canadian Standards under File E 60685
MOUNTING AND GENERAL WIRING:
1. Each timer is to be mounted in a dust tight and water tight NEMA rated enclosure.
2. It is recommended that conduit openings/holes be placed in the bottom of the enclosure
to prevent condensate or moisture from entering enclosure.
3. Mount the timer enclosure in a vibration-free area. (Use isolators to mount timer to sub
plate.)
4. Run supply wiring to the timer, 120Vac, 1 Phase, 50/60 Hz from the line circuit protector.
5. Run wiring from the timer to the pilot valve box.
6. SWITCH (SW1) position must be placed per mode of operation desired.