Page 15 of 33
Failure phenomenon
Operation lamp
Timer lamp
Over current protection of the compressor occurs 4 times
X
☆
No Yes
Yes
No
Failure phenomenon
Operation lamp
Timer lamp
EEROM error
On
☆
EEROM error, indoor PCB is defective.
Failure phenomenon
Operation lamp
Timer lamp
No over-zero signal
☆
☆
This is alarm signal when the main chip can’t detect over-zero signal. When such failure occurs, the main
control board must have fault.
7.2 Outdoor unit
Failure phenomenon
LED1
LED2
LED3
Stand by
☆
☆
☆
High temp. protect of condenser
☆
☆
Temp. sensor in condenser 1 is open circuit or short circuit
☆
Temp. sensor in condenser 2 is open circuit or short circuit
☆
☆
Flash at 2Hz
Operation lamp off and Timer lamp flashes
Indoor PCB is defective
Power supply fault
Outdoor unit fault (such as the compressor)
The voltage of power supply is too low (less than 187V)?
After changing the main control board, check if the failure releases
.
Yes