Installation manual

13

If multiple drying cabinets or dryers are connected to the same air duct, a non-return valve must be installed on each
appliance to prevent cold air from entering or the air pressure of one appliance affecting the other.

fig.W01243

Number of
cabinets

1

2

3

4

5

6

7

8

9

10

Evacuation pipe

dia.
[mm]

125

160

200

315

315

315

315

315

400

400

Recommended
area for fresh air
intake

[m

2

]

0.061

0.101

0.157

0.390

0.390

0.390

0.390

0.390

0.628

0.628

Minimum area for
fresh air intake

[m

2

]

0.035

0.069

0.104

0.139

0.174

0.208

0.243

0.278

0.313

0.347

Содержание DC6-8

Страница 1: ...Installation manual Drying Cabinet DC6 8 Original instructions 427001186 EN 2022 02 03 ...

Страница 2: ......

Страница 3: ...5 1 Placement 9 5 2 Mechanical installation 9 5 3 Narrow spaces 10 6 Evacuation system 12 6 1 Fresh air 12 7 Electrical connection 14 7 1 Connecting an external payment system 16 8 Function check 18 9 Disposal information 19 9 1 Disposal of appliance at end of life 19 9 2 Disposal of packing 19 The manufacturer reserves the right to make changes to design and component specifications ...

Страница 4: ......

Страница 5: ...supervision or instruction con cerning use of the appliance in a safe way and understand the hazards involved Children shall not play with the appliance Cleaning and user maintenance shall not be made by children without supervision Additional requirements for other countries This appliance is not intended for use by persons including children with reduced physical sensory or mental ca pabilities ...

Страница 6: ... 3 Air outlet 4 Elux decal 5 Air flow decal A B C D E F G H I J K mm 1200 580 1820 1635 185 811 529 450 215 600 850 Exhaust air connection 125 mm maximum permitted pressure drop 70 Pa which corresponds to a straight pipe with a length of approx 23 m 160 mm corresponds to a straight length of approx 70 m Net weight 134 kg ...

Страница 7: ...Installation manual 7 3 Installation kit IM OM D x4 A x2 B x2 C x4 E x2 fig W01226 A Screw T6S 6x75 B Washer 8 4x17x1 6 C Wall plug D Cover plug 15 12 E User Manual Installation Manual ...

Страница 8: ... PET 1 Plastics 3 Cardboard protection bars top PAP 20 Paper 4 Cardboard protection bars corners PAP 20 Paper 5 Cardboard protection bars PAP 20 Paper 6 Undercarriage protection FOR 50 Wood 7 Plastic cover LDPE 4 Plastics 8 Green tape LDPE 4 Plastics 9 Wrapping film LDPE 4 Plastics 10 Plastic bag LDPE 4 Plastics 11 Plastic bag LDPE 4 Plastics ...

Страница 9: ...el with each other 5 1 Placement The drying cabinet should be positioned so that there is plenty of room for working both for the user and service personnel 5 2 Mechanical installation The drying cabinet must be secured to the wall to prevent it from tipping over The wall brackets are secured at the top of the drying cabinet upon delivery Remove the wall brackets turn them over and mount as shown ...

Страница 10: ...e height by 185 mm Loosen the two screws Torx T20 on the underside of the front panel square holes in the frame Slide the front panel upwards until it detaches from the guide flanges Then remove it fig W01240 Remove the four screws T20 securing the door switch bracket and then slide it back towards the inner bearing fig W01241 ...

Страница 11: ...Installation manual 11 Remove the four screws T30 from the front and rear rail sitting in the ceiling of the drying cabinet fig W01242 The upper part of the drying cabinet can now be removed ...

Страница 12: ... the humid air that is vented out The area of the air intake must be five times larger than the area of the evacuation pipe The resistance in the grid damper must not exceed 10 Pa 0 1 mbar 5 x A A fig W01229 The drying cabinet works most efficiently if the air flow is optimal The top of the drying cabinet houses a damper that can be adjusted to a value equal to the pressure drop in the duct The ma...

Страница 13: ...entering or the air pressure of one appliance affecting the other fig W01243 Number of cabinets 1 2 3 4 5 6 7 8 9 10 Evacuation pipe dia mm 125 160 200 315 315 315 315 315 400 400 Recommended area for fresh air intake m2 0 061 0 101 0 157 0 390 0 390 0 390 0 390 0 390 0 628 0 628 Minimum area for fresh air intake m2 0 035 0 069 0 104 0 139 0 174 0 208 0 243 0 278 0 313 0 347 ...

Страница 14: ...n all pole circuit breaker Heating options Mains voltage Hz Heat output kW Total output kW Recommended fuse A Electrically heated 230V 1N 50 6 0 6 2 30 400V 3N 50 6 0 6 2 10 Loosen the two screws Torx T20 on the underside of the front panel square hole in the frame Slide the front panel upwards until it detaches from the guide flanges Then remove it fig W01240 ...

Страница 15: ...ing cabinet A fig W01244 Connect the ground cable and the other cables as illustrated 230V 1N Ext Fan 230V 50Hz Pos 17 Pos 5 8 2 1 L1 N PE 400V 3N Ext Fan 230V 50Hz Pos 5 Red L3 12 11 10 9 8 2 1 Brown L2 Black L1 Blue N L1 L2 L3 N PE Reinstall the front panel when you are done ...

Страница 16: ...detaches from the guide flanges Then remove it fig W01240 Connect the cables of the external payment system to the connections A If run information is needed it is found on the two pin contacts on the right Aa A requires potential free switch In other words the signal comes from the card and must not receive any more voltage Aa is a potential free relay that can handle 250 VAC Aa A 1 1 2 1 2 2 3 4...

Страница 17: ...1248 If the drying cabinet is not connected to an external payment system all eight DIP switches must be in the OFF posi tion for the drying cabinet to start ON DIP 1 2 3 4 5 6 7 8 fig W01249 Note The relay output of the payment system must be closed during the entire drying process If this is not the case heating will not work The fan will run but heating will not be activated ...

Страница 18: ...henever a repair has been made a function check must be performed before the appliance can be used again Select any program and check that the drying cabinet is heating and that there are no odd noises Ready for use If all tests are OK the appliance is now ready for use If any of the tests fail or deficiencies or faults are detected please contact your local service organization or supplier ...

Страница 19: ...cycled and that the refrigerator and heat pump components are special waste assimilable with urban waste The symbol on the product indicates that this product should not be treated as domestic waste but must be correctly disposed of in order to prevent any negative consequences for the environment and human health For further information on the recy cling of this product contact the local dealer o...

Страница 20: ...Electrolux Professional AB 341 80 Ljungby Sweden www electroluxprofessional com ...

Отзывы: