Electro-Sensors LRB1000 Скачать руководство пользователя страница 2

Figure 4: Explosion proof 907 Sensor and Pulser Disc

Figure 5: Explosion proof 907 Sensor and Pulser Wrap

Sensor Connection Table

Terminal

Sensor model

906/907

Other ESI 

Sensors

Type NPN

ESI Prox

Type NPN

5 Supply

Red

Red

Brown

6 Signal

Black

White

Black

7 Common

White/Shield

Black/Shield

Blue

Power Input Table

Terminal

12 & 24 VDC

115 VAC

230 VAC

2

(+) Positive

Hot

Hot (L1)

10

(-) Negative

Neutral

Hot (L2)

Relay Connections

Terminal

Setpoint 1

Terminal

Setpoint 2

1

Common

11

Common

3

N.O.

9

N.O.

4

N.C.

8

N.C.

LRB 1000/2000

LRB 2000 ONLY

�������

������������

����������

����������

����������

����������

���������������

���������������

������

������ ������

������

������

������

������������

���������������

������

���������

Figure 3: Base Wiring Diagram

Switch 1

Set Point

������������������

�����������������������������

����

����

��

�����

�����

���

����

�����

���

��

ON

1 - 100 RPM

OFF

10 - 1000 RPM

Switch 2

Mode

ON

Underspeed

OFF

Overspeed

Figure 6: Setpoint Setup

There are 3 steps to calibrating the LRB 1000/2000

1. Determine whether the relay should de-energize when the shaft 

speed drops below the set point speed (Under Speed Operation,) or 

when the shaft speed goes above the set point speed (Over Speed 

Operation.) Use the Over/Under Speed Selection Switch to place the 

LRB 1000 in the desired mode (see Figure 6, for switch position.) 

2. If the set point will be set to trip the relay at a speed below 100 rpm, 

set the Set Point Range Selection Switch to the 1-100 rpm range. If 

the set point will be set to trip the relay at a speed that is above 100 

rpm and below 1000 rpm, select the 10-1000 rpm range

3. Set the Rotary Set Point Switches to the desired set point speed. The 

switches can be set at any number from 01 to 99.

For example:

             

If the RPM Range Selection Switch is set in the 1—100 rpm Range and 

the desired set point speed is 50 rpm, the Set Point Switches should be 

set to 50. In the 10 to 1000 rpm range, the set point is 10 times the switch 

setting (i.e. a switch setting of 80 results in a set point of 800 rpm.)

NOTE:  

Calibration should be done with power to the LRB 1000 turned 

OFF. If a change is made to the calibration while power is ON (Not 

Recommended,) cycle power to the unit. This will store the new set point.

The standard pulser disc or wrap will produce 8 PPR.  

2-4

Free Catalog and Application Assistance

1.800.328.6170

Website: www.electro-sensors.com

990-001300 Revision E