08/30/2007 8
EI203
ELECTRICAL HOOKUP
Note
: All heat/cool functions for this dual heat system originate from a standard 4-wire (heat/cool) room
thermostat. Do not install with a 2-stage heat/1-stage cool or a heat pump room thermostat. Also do not
install using two individual thermostats.
1.
24Ø VOLT SOURCE - Route and wire from the appropriate service entrance panel directly to the
HeatChoice circuit breakers, use only
copper
connected to breakers. The service entrance disconnect and
24Ø volt wire shall be sized according to the HeatChoice nameplate rating. The circuit breakers within this
unit qualify as the appropriate local disconnect.
-
If using single-feed wiring (15 or 20 kW), optional CB bus bars are available, order
EM-
5716
(25 kW, EM-5717).
2.
GROUNDING - Route and install the appropriate size conductor wire between the HeatChoice lug labeled
"ground" and the building service entrance panel ground bus. Use NEC code requirements for grounding
wire size. The conduit is not a sufficient ground conductor.
3.
CONTROL WIRING (reference schematic ES201) – The section assumes gas furnace has an appropriate
fan center or appropriate equivalent wiring terminals with 40VA or larger integral transformer and blower
relay with “G” function.
a.
Room thermostat – use only basic 4-wire, heat/cool type. Route the standard R, W, G, Y roomstat
screw functions to the HeatChoice DHC control board top tab/screw terminal adapters. Use wire to
wire same letter connection.
b.
Air conditioning, outdoor unit – this should be a 2-wire hookup, typically represents the contactor
coil. Connect one wire to the top “Y2” terminal and the second to a bottom “C” terminal.
c.
Gas (or oil with fan center) furnace – the furnace should have a 4 or 5-wire terminal block and
match the control board bottom four terminals – R, W, G, C.
-
The furnace may also contain a “Y” screw, this is only needed if it is a variable speed (DC