3

 

BI502 

Also there are LED’s associated with the thermostat action and the zone valve action.  This greatly simplifies 
wiring and future troubleshooting with a neat terminal block wiring arrangement and the onboard LED’s – 
order EB-ZT*-1. 

2.

 

Prevents over control or false staging up and down when the temperature sensors are attempting to 
regulate

 – since Electro Industries’ zone controller also has staging “smarts”, the addition of the zone 

controller will provide smoother boiler temperature control.  The zone board has a dial switch for each zone 
and the installer selects one of four zone capacity sizes.  When dialing in the size closest to the zone Btu/h 
capacity, the zone controller “smarts” only allows the appropriate boiler stage which can handle that capacity.  
Also this is additive if more than one zone calls at any one time – order EB-ZT*-1. 

3.

 

Two temperature system with unbalanced zones

 – if the application includes zone one requiring high 

temperature (fin tube, air handler, etc.) and the remaining zones are radiant floor low temperature, this zone 
controller (EB-ZT*-1) will automatically raise the output of the high temperature zone.  This is a priority 
arrangement, zone 1 holds off the other zones while the high temperature output is heating.  If at the end of the 
high temperature zone there is a call on any of the low temperature zones (up to three plus slave 4), there will 
be a pump only function until the outlet temperature drops below the front panel dial setting. 

 

Field zone controller installation

 – the above mentioned zone controller board is installed within the 

basic cabinet.  

However

, the zone controller board must communicate with the main TS boiler board.  All 

units manufactured prior to approximately January 10, 2004 may need a controller program chip upgrade.  
Verify your unit is Ver. 6.20 or higher. 

 

ZONE CIRCULATORS 

The EE-5051 switching relay can be used to interface line voltage pumps with the boiler R and W control 
terminals, see drawing BH008.  This switching relay can be combined with the above zone controller 
board. 

 

ROOM THERMOSTAT PLACEMENT 
Fin tube radiation, fan coil, etc. – 

heat only wall t-stat, connected to operate zone valves (see previous 

section) or for single zone the t-stat is connected directly to Electro-Boiler R and W. 

 

Floor radiant

 – comfort and proper space heating response is a direct relationship to the thermostat type 

and the placement of the thermostat sensing bulb.  Typically an under floor heating system can be broken 
down into three categories. 

A.

 

Energy storage, water tubing is under the concrete or within the sand 
base

 – the controlling thermostat must have a remote bulb, and this remote 

bulb must sense the concrete slab temperature (slab stat).  Coordinated with 
the concrete pour, install a ¾” PVC, minimum bend radius of 7 inches, and 
locate at approximately center (vertical) of the concrete slab.  The thermostat 
sensing bulb can later be pushed down this PVC conduit.  If the slab is already 
poured without conduit for slab stat, use electronic remote sensing thermostat 
such as Electro Industries’ 

ES-24-SRO or ES-24-C-RS

.  These devices only 

require a ¼” hole drilled in the floor at some convenient location (preferably 
off a center wall, not within 2 feet of outside wall). 

B.

 

Floor covering, medium to high insulation 

– use slab stat as described in paragraph A above. 

C.

 

Quick response, hydronic tubing just under the concrete surface, no flooring material over the concrete

 

– in this case, heated water can directly radiate into the room, a standard wall mount room thermostat is 
adequate.  Mount room thermostat on an inside wall similar to most heating systems. 

 

MULTIPLE BOILERS 

 

This boiler series now includes a method for automatically staging any 
number of parallel-plumbed boilers.  Order plug-in relay EB-C-STG5. 

 

The thermostat is connected only to the first boiler, when all stages are 
on for more than 5 minutes, this new plug-in relay module turns on the 
next boiler (R and W), and a second EB-C-STG5 could be used to turn 
on the third, etc. 

 

Содержание Electro-Boiler EB-WO-13

Страница 1: ...ertemp conditions With the mixture of zones the zone controller ZTS option is highly recommended see page 2 This series is equipped for load management interrupt and can apply to standard baseboard radiation dual heat combinations under floor radiant wood boiler supplement etc Note If this installation does not include dual heat standby boiler the front panel switch must always be in the normal po...

Страница 2: ...ple Boilers 3 Two Temperature Operation or Feature 4 Boiler Plumbing Kit Placement 4 Installation Requirements 4 Mechanical Installation Under Floor Radiant 6 Dual Heat 7 Electrical Hookup 8 Standby Boiler 9 Remote Display 9 Water Fill Procedure 9 Controller Setup 10 Operational Tips 12 Replacement Parts List 13 Troubleshooting Repair Helps 13 WarmFlo Operational Information 14 ...

Страница 3: ...l the Electro Boiler is generally at the gas oil outlet but for wood the Electro Boiler must be on the inlet sides The standby boiler cannot be operated as hot boiler This will defeat the Electro Boiler Rewire as required standby boiler is turned on from the brown wires In the case of existing fossil fuel boiler conversions it is assumed the expansion tank valving air bleeder and circulation pump ...

Страница 4: ...ly injection pump techniques come with a controller which is designed to protect a gas boiler from cool water return This is simply not needed and a duplication with the temp sensing controller within this Electro boiler and the injection pump controller will be of no benefit within the operating system The zone valve zone pump control strategy must be wired to provide the boiler R and W contact c...

Страница 5: ...erface line voltage pumps with the boiler R and W control terminals see drawing BH008 This switching relay can be combined with the above zone controller board ROOM THERMOSTAT PLACEMENT Fin tube radiation fan coil etc heat only wall t stat connected to operate zone valves see previous section or for single zone the t stat is connected directly to Electro Boiler R and W Floor radiant comfort and pr...

Страница 6: ...k must be performed by trained qualified contractors or technicians Electro Industries Inc sponsors installation and service schools to assist the installer Visit our web site at electromn com for upcoming service schools WARNING ALL ELECTRICAL WIRING MUST BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE AND LOCAL ELECTRIC CODES ORDINANCES AND REGULATIONS WARNING OBSERVE ELECTRIC POLARITY AND WIRING C...

Страница 7: ...staller must know this product well enough to instruct the end user on its safe use Safety is a matter of common sense a matter of thinking before acting Professional installers have training and experienced practices for handling electrical sheet metal and material handling processes Use them CLEARANCES MINIMUM CLEARANCE FROM COMBUSTIBLE SURFACES SUGGESTED MINIMUM SERVICE CLEARANCE BACK 0 INCH 0 ...

Страница 8: ...d This can be an air diaphragm tank as provided in the plumbing kit or a basic empty tank where air is compressed at the tank top Inlet Temperature Gauge recommended to observe the operation of the system Air Vent install with the pressure relief valve as shown on drawing BX502 page 2 or part of the air eliminator shown on BX502 page 3 Inline Air separator this can be installed ahead of the pump w...

Страница 9: ...top The unit will not function properly with the vessel in a horizontal position NOTE Mount at least 20 inches above the floor to allow element removal and service at the bottom 5 Typically this unit is wall hung next to the existing boiler 6 Use the pipe fittings to install the safety relief valve and air vent Add the necessary piping to the safety relief valve so that water damages do not occur ...

Страница 10: ...ally check valve isolate the standby boiler self contained pump from the system pump controlled by these two terminal screws 4 Operating Thermostat two types can be used Connection is at the control board bottom Standard Mechanical connect to R and W bottom right Set thermostat internal heat anticipator to 0 2 Electro Stat ES 24 C RS or ES 24 SRO 3 wire connection required R to R W to W C to commo...

Страница 11: ... the recommendations and source from your local professional plumber specializing in hydronics heating systems WATER FILL PROCEDURE The following procedure applies to non glycol or antifreeze and prepackaged plumbing kit and or when the system is plumbed exactly as shown on drawing BX502 Caution If the building supply pressure is connected directly to supply water ball valve without pressure reduc...

Страница 12: ...cal 67 outside NOTE The customary definition of outdoor reset is basically opposite to this Electro Industries WarmFlo concept In the case of outdoor reset you set the maximum or worst condition operating supply temperature As it warms up outside the supply temperature is decreased downward from that point In the case of Electro Industries WarmFlo we begin at a minimum or comfort level supply temp...

Страница 13: ... during load control interrupt On the inside control board just above the two bottom terminal blocks is a small pin jumper arrangement The black device sets up the pump mode Just below this pin jumper arrangement are W and L lettering When the two pin shorting device is in the W position the pump is a direct function of R to W input When the two pin jumper is in the L position the pump is interrup...

Страница 14: ... light indicator associated with these safety hi limits Also these 205 F safety limits break the L2 current carrying 240 volt wire going to the elements Reset involves locating a small shiny lever or metal tab protruding on the side of the black safety limit base This small tab is pressed inward approximately 1 8 to snap in the contacts Safety caution the wires and screws have 240 volt potential a...

Страница 15: ...ram from standard PC or Analyzer software This includes the ability to fool the sensor or set in an offset for various troubleshooting purposes This software disk comes with a special cable needed for PC or Analyzer hookup ET SOFT TS PC software disk and cable ET SOFT TSP Palm software disk and cable 4 The terminal blocks for control wire hook up are designed for a wire insertion and screw clamp d...

Страница 16: ...nctions STANDBY RESET allows disable of 5 minute 80 reset SOT E time or disable all stages on DT flat Stage disable temperature 1 2 3 4 Applies mainly to EBWO for EBWA OT function is disabled Warning field reprogramming within WarmFlo II internal logic and non volatile memory it can detect whether it is operating from one of the above factory pre programmed chips or if it has been modified reprogr...

Страница 17: ...for each stage allowing the disable of specific stages above the preset temperature Delay transfer from standby to electric if the unit was operating in SB for more than 1 minute the follow up transfer back to electric engages a 2 minute delay before any of the electric stages are activated The pump will react to the call for heat but the elements will stay off for 2 minutes in order for the pump ...

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ...tem for Brand X boilers or dual EB R L E Series EB ZC 4 wiring and convenience interface isolated boiler end switch EB 5415A low cost 2 or 3 zones sheds one boiler stage Mini Boiler enhancement ZONE CONTROLLER SLAB STAT Sensing and controlling the system based upon radiant floor surface temperature or the concrete mass has very positive benefits Radiant floor air stat in the same area as a forced air...

Страница 26: ...es boilers come standard equipped with outlet temperature pressure gauge pressure relief safety valve and when applicable the WarmFloTM electronic control sensors These kits provide the additional components for easy installation 5585 Mini Boiler 10 kW TS Series 5586 TS Series Standard 5578 3 4 Pipe 5582 1 Pipe 5579 1 1 4 Pipe 120V 1 25 HP maintenance free wet rotor circulator Pump curve example 5...

Страница 27: ...ade by Electro Industries or its authorized representative Electro Industries will cover reasonable labor costs to repair defective product or product parts for ninety 90 days after installation TWENTY YEAR 20 LIMITED WARRANTY ON BOILER ELEMENTS AND VESSELS Electro Industries Inc warrants that the boiler elements and vessels of its products are free from defects in materials and workmanship throug...

Страница 28: ...ill be null and void 4 The purchaser shall have maintained the product in accordance with the manual that accompanies the unit Annually a qualified and licensed contractor must inspect the product to assure it is in proper working condition 5 All related heating components must be maintained in good operating condition 6 All lines must be checked to confirm that all condensation drains properly fr...

Отзывы: