background image

EDA-Z5008, Z5020 & Z5100 – User Manual  

 

 ZPControlUserMan_r100 

_____________________________________________________________________________________________________ 

 

14 

 

6.0 - Test Mode 

 

Test mode allows a system to be tested with minimal disruption to the occupants of a building. When a 
zone  is  placed  into  test  mode  the  engineer  can  choose  to  disable  sounders,  actuators  or  any  output 
devices.  Should  anything  happen  outside  of  these  selected  zones  the  system  will  operate  as  normal 
and the sounders will sound.   
 
Once the various Test Mode parameters have been chosen, the Test Mode LED will illuminate on the 
main panel. Once selected, the option is also given to save the parameters so that they can be used for 
subsequent  test  mode  operations.  When  a  zone  has  been  put  into  the  Test  condition,  subsequent 
alarms from devices in that zone do not appear on the Main Screen as an alarm, but appear as a “FIRE 
TEST” event in the event log.  
 

6.1 - Test Zone – advanced, service and commissioning users

 

 

1.Main Menu>>3.Test Mode>>1.Test Zone 

Scroll to the appropriate zone number using the 

 or 

 keys, and 

press the 

 key to select that zone. Follow the on screen prompts 

to set the test parameters. 
 
Sounders: 

If sounders within the zone are to be disabled, select 

‘NO SOUND’

. Alternatively the sounders can be set to 

‘6  SEC  SOUND’

,  where  any  activated  sounders  will 

automatically silence after 6 seconds. This allows the 
engineer  to  perform  a  one-man  walk  test,  without 
the need to return to panel to silence the alarm. 

 
Timeout: 

This  is  the  amount  of  time  before  the  system  will 
automatically  exit  test  mode  operation.  A  timeout 
period of ‘0’ means that the zone will remain in test 
indefinitely,  until  the  test  is  disabled  by  the  user.  In 
order  to  operate  this  panel  and  comply  with  EN54 
part  2,  this  setting  should  not  be  set  to  anything 
other than ‘0’. It can be set in 1 hour intervals and is 
selected using the cursor keys. 

 
 
Once completed, press 

Enter

 to place the zone into test mode with the chosen settings. ‘Zone XXX in 

Test’ will be displayed on screen and the ‘Test Mode’ LED will illuminate. Multiple zones can be tested 
at the same time, by selecting ‘Enter more Zones’. The zone tests will be visible in the 

‘5-Tests’

 section 

of the quick menu.  
 

6.2 - Clear Zone in Test – advanced, service and commissioning users

 

 

1.Main Menu>>3.Test Mode>>2.Clear Zone in Test 

This option allows the user to cancel test mode for a zone currently 
in test. Select the zone and press 

Enter

. If no zones are in test the 

display  should  show  the  screen  opposite  and  the  ‘Test  Mode’  LED 
will extinguish. Press 

Cancel

 to return to the menu. 

 
      Zone 001↕ 
 
 

Use ← → keys 

 

Select Tone 

 

 NO SOUND↕ 

 
 

Use ← → keys 

 
  Timeout (hrs) 001↕ 
 
 

Use ← → keys 

 
  No Zones in Test 
 
   CANCEL to exit 

   

 Zone 001  

 

 in Test 

 
  ENTER to continue 

Содержание ZERIO PLUS EDA-Z5008

Страница 1: ...ZERIO PLUS EDA Z5008 Z5020 Z5100 USER MANUAL ZPControlUserMan_r100 Revision 1 00 ...

Страница 2: ...EN54 2 1997 A1 2006 EN54 4 1997 A1 2002 A2 2006 EN54 25 2008 Control and indicating equipment for fire detection and fire alarm systems for buildings Models EDA Z5008 EDA Z5020 EDA Z5100 Optional functions with requirements 7 8 Output to fire alarm devices 7 9 1 Output to fire alarm routing equipment 7 11 Delays to outputs 7 12 Dependency on more than one alarm signal Type C dependency 7 13 Alarm ...

Страница 3: ... Z5020 Z5100 User Manual ZPControlUserMan_r100 _____________________________________________________________________________________________________ 3 Revision History V1 00 19 01 2015 User manual first release ...

Страница 4: ... Part 25 Based on the popular Zerio system the updated Zerio Plus has been designed to be capable of handling 240 devices in 100 zones Typical installations would include small offices private houses HMO s guesthouses and small hotels This manual contains information to enable a user to operate the Zerio Plus control panel and the range of Zerio Plus devices This product should be installed commis...

Страница 5: ... 0 User Operation 2 1 System Normal 2 2 Fault Conditions 2 3 Silence Buzzer 2 4 Reset a Fault 2 5 Alarm Conditions 2 6 Silence the Alarm 2 7 Re sound the Sounders 2 8 Reset the Alarm 2 9 Access Levels 3 0 Menu Operation 3 1 Quick Menu 4 0 Setup Menu 4 1 Time and Date 5 0 Disable Enable Menu 6 0 Test Mode 6 1 Test Zone 6 2 Clear Zone In Test 6 3 Lamp and Buzzer Test 7 0 Faults 8 0 Maintenance ...

Страница 6: ...on exists across multiple zones multiple zone LEDs will be illuminated The zone LEDs will remain lit until the panel is reset The EDA Z5008 8 Zone panel is shown The EDA Z5020 panel is equipped with 20 zone LEDs and the EDA Z5100 is equipped with 100 zone LEDs Status LEDs Supply This LED will be illuminated when mains power is present Delays Active Illuminated if delays are enabled Disablements Il...

Страница 7: ... a number of functions Cancel Used to return to the main screen from a menu or to return to the menu from a programming screen Enter This is used to accept information programmed into the panel Re sound Alarm Following an alarm condition that has been silenced but not reset this button will re sound the alarm Silence Alarm If the panel is in a fire condition this will silence the sounders Silence ...

Страница 8: ...been pressed the panel assumes that the fault has been acknowledged and does not re sound the buzzer unless a new fault occurs The LED on the device will continue to flash until the fault is reset see below 2 4 Reset a Fault A fault will be displayed on the panel until the system is reset even if the fault condition has been rectified Assuming the fault has been rectified pressing Reset on the pan...

Страница 9: ...alarm i e the glass has not been replaced in a callpoint or a smoke detector detects smoke is still inside the unit after silencing the alarm and pressing Reset the panel will redisplay the alarm and the sounders will sound again 2 9 Access Levels The panel is protected from misuse by means of four access levels The access levels are as follows Level 1 Untrained user Level 2A Basic user Level 2B A...

Страница 10: ...in Menu 4 View Events 2 View Event Log If a non menu screen is selected the Cancel button should be pressed to return to the menu without making any changes Subsequently then pressing Cancel for a second time will return to the system screen If any changes are made to settings these are generally saved using the Enter key as detailed on the display If an alarm occurs while in menu mode the menu wi...

Страница 11: ...d the LED marked Disablements will now be illuminated on the panel After the timeout period has elapsed the isolated zone s will automatically be re enabled Disable a Device all access levels 1 Main Menu 2 Disable Enable 1 Disable 2 Device If a device is disabled the system will not display any fire or fault events for that device Using the or keys select the device number to be disabled and press...

Страница 12: ...ble LED will be illuminated After the timeout period has elapsed any disabled sounders will automatically be enabled again When sounders are disabled any hard wired sounder circuits will not display short circuit and open circuit faults Disable Fire Routing all access levels 1 Main Menu 2 Disable Enable 1 Disable 5 Fire Routing The fire routing relay can be disabled for a period of time specified ...

Страница 13: ... have been enabled No Devices to enable will be displayed If a previously disabled device is enabled and no other isolated devices zones remain then the Disablements LED will extinguish Enable Panel Input all access levels 1 Main Menu 2 Disable Enable 2 Enable 3 Panel Input Select this option to enable an input that has previously been disabled Choose the input from the list and press Enter to con...

Страница 14: ...ely the sounders can be set to 6 SEC SOUND where any activated sounders will automatically silence after 6 seconds This allows the engineer to perform a one man walk test without the need to return to panel to silence the alarm Timeout This is the amount of time before the system will automatically exit test mode operation A timeout period of 0 means that the zone will remain in test indefinitely ...

Страница 15: ... based on BS5839 codes of practice Daily Actions The user should check that the panel indicates normal operation If any faults exist they should be recorded and the responsible person or maintenance company should be notified Weekly Actions The user should put at least one callpoint or detector in to alarm checking that the correct device zone is indicated on the panel and that the programmed soun...

Страница 16: ...th LED Beacon 2 x EDA Q690 EDA T5000 Radio Transmitter Unit 1 x EDA Q690 EDA T5100 Radio Silence Alarm Button 1 x EDA Q690 EDA T6080 Radio Input Output Unit DC 1 x EDA Q690 EDA Y5000 Dipole Weatherproof Antenna EDA Z5008 8 Zone Radio Control Panel EDA Z5020 20 Zone Radio Control Panel EDA Z5100 100 Zone Radio Control Panel EDA Z6000 Radio Booster Panel with I O EDA Z6001 Radio Booster Panel EDA Z6...

Отзывы: