kept from sitting in the sludge which will collect in the 
bottom of the tub. 

Never allow the cell or ionizer to 

sit longer than 15 minutes in the DAX or they will 
discolour. 

The tub should be covered when not in 

use to prevent evaporation. 

8.  Spray the prefilter and after filter with 

DAX Detergent

 

and rinse well, applying water pressure against the 
air flow direction. This pushes contaminate out of the 
filter instead of forcing it through the filter.. 

9.  To dry the cell and ionizer, tilt on a 45º angle against 

wall with the direction arrow pointing sideways. Allow 
to dry completely for at least 8 - 10 hours. 

10.  When the cells, ionizers, prefilters and after filters are 

dry, install them back into the cabinet. 

The arrow on 

the cell and ionizing section should point toward 
the blower. The spring contact should line up 
with the fibreboard on the back wall of the 
cabinet.

 Close the door. If the cells arc when the fan 

and power supply switches are turned on or if the 
performance indicator light does not come on, then 
the cells may still be wet. Allow more time for drying. 
You can leave the cell and ionizer in the unit, turn the 
fan switch 

ON

 and leave the power supply switch 

turned 

OFF

 

A cell placed in the air cleaner incorrectly can 
burn out the power board.

  

 

11. The high voltage contact boards inside the cabinet 

need to be cleaned on a regular basis to insure a 
good contact with the cell and to prevent 
accumulation of contaminate behind the contact 
board. Clean the contact disc and surrounding red 
contact board with a dry cloth while the accumulation 
behind the contact can be removed with dry 
compressed air. Complete access to the back of the 
contact boards can be made from the outside of the 
cabinet by removing the small panels on the back 
side of the unit. The high voltage wires near the 
contact boards should be wiped when the contacts 
are cleaned and inspected annually by a qualified 
service technician for deterioration.  

12. The accumulated contaminate under the cells and in 

the blower compartment should be removed at least 
twice a year with a vacuum. Dry compressed air can 
be used to remove the dust in the switch box and 
power box which houses the high voltage power 
supply. Do not apply air pressure too close to the 
components as this may damage them. Build up of 

contaminates on the blower wheel and housing can 
also be cleaned with dry compressed air. The motor 
should also be blown off with dry compressed air or 
vacuumed, particularly around the cooling fan intake 
at the back of the motor. 

 
CLEANING AND SERVICE 
 

The use of 

DAX Detergent

 is recommended for cleaning 

as it is a heavy duty solution used expressly for removal 
of accumulated pollutants on cell plates. If used as 
directed, 

DAX

 will not harm aluminum or steel if used as 

directed. Any problem arising out of the use of another 
cleaning agent will void the warranty. 
 

DAX Detergent 

is available in 1 gallon (4.5 L) and 4.4 

gallon (20L) containers, as well as 45 gallon drums (205 
L). 

 
 
SERVICE MAINTENANCE

 

 
1.  Determine if the air cleaner is performing properly by 

seeing that: 

 

• 

Fan switch is 

ON

 

• 

Power Supply switch is 

ON

 

• 

Performance indicator light is 

ON

 

2.  The performance indicator light, when lit, shows that 

the power board is functioning properly and should be 
lit during normal operation. The light will flicker with 
arcing in the cell or extinguish if the cell, ionizer or 
power board is shorted. 

3.  If the performance indicator light fails to light, check 

the cells to ensure they have been installed properly. 

4.  If the light still does not come on, remove the cells 

and ionizers and close the door. Turn the unit on. If 
the light now comes on inspect the cells or ionizers 
for damage or water. Check the high voltage wires for 
deterioration. 

Do not run the unit for more that 1 

minute with the cell and ionizer removed.

 If the 

light still is not on then the problem could be in the 
light or the power board. Check the fuse on the power 
board for continuity.  

5.  A simple test to ensure that the cell is in correctly and 

there is high voltage to the cell is to take a long 
plastic handle screwdriver and short the cell between 
the frame of air cleaner and bolt head on the 
porcelain insulators. Check both the cell and ionizer 
for a spark. The fan and power supply switches 
should be 

ON

. Be sure to activate the safety interlock 

switch before checking the voltage. 

CAUTION: You 

are dealing with high voltage.

 

6. 

If in doubt and if cell is not collecting any carbon, tars 
or body shop dust, then consult your dealer or factory 
service center. The installing dealer should have 
sufficient knowledge to determine any problems.

 

WARNING  

Wear protective goggles, dust mask and gloves when 
cleaning the inside of the cabinet. Always turn both the 
fan and power supply switches 

OFF

 and 

turn OFF the 

main breaker and lock out

 the unit before cleaning. 

 