SERVICE INDICATION

SERVICE CHECKS

ON/OFF switch “ON”

Unit functioning Normally

Blower ON
Operating Light ON

ON/OFF switch “ON”

1.

Power is not being supplied to air cleaner.

Blower ON

A. Check fuse or circuit breaker.

Operating Light OFF

B. Ensure power pack is properly installed and latched.

2.

Collecting cell shorted - Turn power Off -  Remove power pack - Remove
 collecting cells - Replace power pack - Restore power (ensure blower is
operating).
A. If Operating Light comes ON check cells for bent plates, loose ionizing

wire(s) or cracked insulator(s).

B. If Operating Light remains OFF, malfunction is in the power pack. (See

power supply Checkout Procedure).

ON/OFF Switch “ON”

1. Air flow sensor contaminated/misaligned

Blower OFF

A. Remove power pack and clear contamination inside black bushing around

Operating Light ON

the small sensor element.

B. Ensure small sensor element is centered in bushing.

2. Air sensor left in bypassed condition after servicing.**
3. Faulty air flow sensor panel.

Excessive arcing during

1. Wet collecting cell.

normal operation -

A. Allow cell(s) to dry after cleaning before applying power.

Operating Light may blink

2. Damaged collecting cell(s).

A. Remove cell(s) and inspect for bent plates, loose ionizing wire(s), cracked

insulator(s), etc.

3. Collecting cells dirty.

A. Clean cells as instructed in this manual.

4. Faulty power supply (see power supply checkout procedure)

**NOTE: Your air cleaner is equipped with an air flow sensor (switch) which turns the unit ON and OFF in re-
sponse to the system blower. It may have been “wired out” during a service check and inadvertently left in this
condition

BASIC SST SERVICE GUIDE

This guide will cover most homeowner complaints. If, after checking the items listed, the unit still fails to operate
properly, contact the nearest Authorized Service Center.

Содержание 10C26S-010

Страница 1: ...Basic SST Service Guide Technical Repair Guide Repair Parts Electronic Air Cleaner Printed In U S A UL Listed CSA Certified by White Rodgers Please read and familiarize yourself with the contents of...

Страница 2: ...unit must comply with local electric codes or other applicable codes Review and understand local codes prior to in stallation Failure to do so could result in serious personal injury or death CAUTION...

Страница 3: ...and maintain Its basic components and their functions are as follows See Figure 2 Cabinet mounts to existing duct work and houses the collecting cells and pre filters Collecting Cells are made in two...

Страница 4: ...ream from the air filter If your furnace duct system has a pre installed boot discard front cover of boot and slide the air cleaner component inside the boot Applies to 14C26S 010 and 20C26S 010 If fu...

Страница 5: ...t offset to match air filter opening If duct connection to furnace allows less than nine inches for mounting the air cleaner shorten the lateral trunk or attach an offset fitting to the elbow HORIZONT...

Страница 6: ...attached directly Figure 13 or a starting collar can first be fitted to the furnace inlet A butt or slip joint can be used Securely attach the cabinet to furnace inlet using at least two of the mount...

Страница 7: ...or connections See Fig 17 Insure all wires are clamped wire connectors prop erly installed and grommets used to prevent wire abrasion 10 With the cabinet Installed reinstall pre filter s and collectin...

Страница 8: ...angle to expedite the drip dry pro cess 7 Reinstall the cell s and pre filter s in the cabinet 8 Replace the power pack Turn furnace fan on After 30 minutes push ON OFF switch on the power pack to the...

Страница 9: ...ely anchored at each end Support Ionizing Wire Figure 21 Rated Capacity 600 1200 cfm 1000 1600 cfm 1000 2000 cfm 1600 2200 cfm Max Pressure Drop 08 in W G 08 in W G 12 in W G 09 in W G Cell Weight 2 7...

Страница 10: ...ng Light ON the small sensor element B Ensure small sensor element is centered in bushing 2 Air sensor left in bypassed condition after servicing 3 Faulty air flow sensor panel Excessive arcing during...

Страница 11: ...injury or death This guide contains service checks to assist service personnel in locating and correcting any malfunction that might occur to render the air cleaner ineffective or inop erative The air...

Страница 12: ...sion cord apply 120 VAC to power pack Turn power switch to ON position 5 Connect meter negative lead to metal frame of collecting cell Use high voltage probe to measure voltage at collecting cell ioni...

Страница 13: ...ially at high altitudes or low air flow rates This power supply has a hairpin shaped jumper wire labeled W1 see Fig 24 that can be cut and separated in case of such complaints This will cause the powe...

Страница 14: ...14 1 2 3 4 5 5 6 2 3 7 8 9 18 5 14 13 10 11 12 REPAIR PARTS...

Страница 15: ...F876 0202 F876 0202 F876 0202 F876 0202 12 Power Pack Cabinet Only N A N A N A N A 13 Connector Male F827 0026 F827 0026 F827 0026 F827 0026 14 Power Supply F858 1000 F858 1000 F858 1000 F858 1000 15...

Страница 16: ...a White Rodgers Electronic Air Cleaner or product containing a White Rodgers Electronic Air Cleaner Although White Rodgers does not extend a warranty directly to consumers White Rodgers does extend a...

Отзывы: