9.000 seconds. When the limit switch goes ACTIVE, the examine
period starts just like in the CAM MODE. However, once the
examine period begins, the Die Sentry begins waiting for the
specified probe TIME setting. At the end of the SET TIME, the
examine period ends. The probe must still be seen as "ON" during
the examine period or a probe fault will occur just as in the CAM
MODE. The reported probe times are still the amount of time it took
the probe to go "ON" after the examine period began. A normal
case is given below.