PLUS96

PLUS96-P

PLUS96-485

AKSE S.r.l. via Aldo Moro, 39 - 42100 Reggio Emilia (RE) - Italy - Tel. +39.0522.924244  Fax. +39.0522.924245

3

INSTRUMENT PROGRAMMING

When the instrument is powered up, WAIT is shown on the display. After a few seconds the
instrument shows the measure (the LED provided on the key is ON). To enter the programming
mode, selector switch located on the rear of the instrument must be set to ON position, press the

key to access programming  

and the key 

simultaneously. Selection of ATs is shown

on the display.

Press the key 

 to select the ratio of available ATs (see AT table)

Once the selection has been completed, press the programming key.
The default settings envisages:
- CT transforming ratio = 5/5
After programming, set the selector switch located on the rear of the instrument to 0 if you wish
to disable the hidden key.

4

RS485 OUTPUT CONNECTION

English

Instructions

After entering the programming page through 

  and 

, press the key 

 once more and

the address of the instrument will be displayed. The default address set by the manufacturer upon
delivery is:

.

It can be changed through: key 

to select the  digit

Key 

 to increase the digit

Key 

to decrease the digit

The flashing digit is active.
To exit the programming, press key 

 a fourth time.

The maximum selectable number is 247.

PLUS96 Y

PLUS96-P Y

PLUS96-485 Y

P R O G R A M

O N

O F F

CT used

Akse  declares that its range of instruments complies with the EMC 89/336/EEC
directive and satisfies the requirements of the following standards: EMISSION = EN
50081-1 1992; EN 55022-CLASS B CISPR 22; IMMUNITY  = EN 50082-1
(light industry) 1992; SAFETY IEC 61010.

1

SAFETY

This instrument was developed and tested in compliance with IEC 1010 and class 2 VDE 411
standards, conforming to the VDE0110  group C insulation standards, for rated  voltages  lower
than or equal to 500 VAC rms (phase-neutral wire).
In order to maintain these conditions and to guarantee safe usage, the user must comply with the
warnings and symbols outlined in the following instructions.
Upon receipt of the instrument and before installing it, make sure that it is sound and did not suffer
any damage during shipment
First, make sure that the rated voltage corresponds to the mains voltage and then install the
instrument
The instrument power supply must not be grounded
The instrument is not equipped with a safety fuse on the power supply. Therefore, it must be
protected by the operator.
Only qualified and authorised personnel is authorised to carry out repairs and/or maintenance
operations.
If you fear that the instrument is no longer safe, disable it and make sure it cannot be used
unintentionally.

The operation is no longer safe:
1 ) If the instrument shows evident damage
2 ) If the instrument does not work
3 ) After a long period of non-use under unfavourable conditions
4 ) After serious damage suffered during shipment

1.1

OPERATOR SAFETY

Read the instructions thoroughly before installing and using the instrument.

The instrument described in this instruction manual is deemed to be used by duly trained personnel.
Only qualified and authorised personnel is authorised to carry out repairs and/or maintenance
operations.
For the correct and safe use of the instrument and for the maintenance and/or repairs, it is extremely
important that the persons in charge follow the normal safety procedures.

1.2

SYMBOLS

READ THE INSTRUCTIONS

2

CONNECTION OF THE VOLTAGE AND CURRENT MEASURES

The instrument is auto-fed by V1 and V2 mains voltages. Use cables with a max. section of 2.5
mm

2

 and connect them to the terminals identified with VOLTS INPUT, according to the wiring

diagram shown in the figure. WARNING: threshold: 60-500VAC phase-phase. You need to use
3 CTs with a 5A  secondary. Connect the amperometric signal from the CTs to the terminals
marked with CURRENT INPUT according to the diagram shown in the figure. Use cables with
the proper section according to the used CT capacity and to the distance.
Note: the CT secondary must always be short-circuited when it is not connected to the instrument
to avoid damage and risks for the operator.

ALWAYS KEEP TO THE PHASE MATCHING BETWEEN VOLTMETRIC AND AMPEROMETRIC
SIGNALS. Failure to follow both the matching and the wiring diagrams may lead to measurement
errors.

Standard auto-fed model

Rev. 06/01

MAX 5 A

L1

L3

L2

S1

S2

S2

S2

V 1      V 2       V 3

I3 I2 I1

1        2        3

5    6    7     8

S1

S1

P1

P1

P1

P2

P2

P2

MAX 5 A

340 ÷ 420 VAC

FASE-FASE

4 wires model

200 ÷ 240 VAC

FASE-NEUTRAL

Отзывы: