background image

ALARM SETTING EXAMPLES

NOTE n.2

POWERS

Integration time of the average value (AVG) and max. value (MD) for power (from 1 
to 60 minutes)

CURRENTS

Integration time of the average value (AVG) and max. value (MD) for power (from 1 
to 60 minutes)

NOTE n.3

NORMAL

Classic alarm with reference to a fi xed or max / min threshold, with applicable 

 

hysteresis and delay. The “ AVG” parameter is not used.

DERIV

The “THRE” parameter becomes a percentage value.
The instantaneous value applied to the alarm on “MEAS“ will be compared with its 
averaged value obtained depending on the time set on “AVG”.
When the instantaneous value combined to the alarm differs in “more then“ (if set 
“MAX”) or in “less then“ (if set “MIN”) compared to the average value (“AVG”) of the 
percentage set on “THRE”, the alarm triggers. With applicable hysteresis and delay. 
The “AVG” parameter is used.

NOTE n.4

MAX

Alarm confi guration in “excess” according to the conditions set.

MIN

Alarm confi guration in “excess” according to the conditions set.

NOTE n.5

MEAS

Indicates on which register (and on which measure) the alarm is reported.
See table n.1 (Input Register).

THRE

Alarm threshold in absolute value, except the “DERIV” value where the value inserted 
becomes a percentage.

NOTE n.6

AVG

Parameter to be used in the sole “DERIV” mode. Floating window amplitude ( in se-
cods) used for creating a  reference value to which compare the instantaneous value.

NOTE n.7
NORMAL

The output remains exited during all the alarm, after all it falls.

HOLD

The output remains exited untill the manual reset made through Modbus

PULSE-L

The output generates a 500ms pulse on the alarm triggering. 

PULSE-S

The output generates a 100ms pulse on the alarm triggering. 

NOTE n.8

PULSE

Enables output function as impulsive

ALARM

Enables output function as alarm

REMOTE

Enables output function through Modbus Protocol

NO

Normally open

NC

Normally closed

NOTE n.9

P-IMP

Imported Active Power (Energy)

P-EXP

Exported Active Power (Energy)

NOTE n.10

YES

Refered to the primary of the CT

NO

Refered to the secondary of the CT

NOTE n.11

ALARM 1

Alarm associated to the physic output DIGITAL OUT 1 (DO1, terminal 8)

ALARM 2

Alarm associated to the physic output DIGITAL OUT 2 (DO2, terminal 9)

ALARM 3

MODBUS only alarm

ALARM 4

MODBUS only alarm

In order that the output “DIGITAL OUT 1” gets excited and remains such during all the 
alarm (latching): when the Average Active Power (MEAS 344) exceeds the value of 100 
kW, hysteresis 5% and delay of 5 seconds, set the parameters as in the table below:

ALARM 1 / A

MODE (

note n.2)

Normal, 1-OF-3, 3-OF-3, DERIV, UNBAL

NORMAL

TYPE (

note n.3)

MAX, MIN

MAX

MEAS (

note n.4)

Controlled measure. See table n.1 for the 
register selection

344

THRE (

note n.4)

Threshold value

100000

ALARM 1 / B

HYST

1...100 (%)

5

DELAY

1...99 (seconds)

5

AVG (

note n.5)

1...99 (seconds)

1

OUT (

note n.6)

Normal, Hold, Pulse-L, Pulse-S

NORMAL

DIGITAL OUT 1

MODE

PULSE, ALARM, REMOTE

ALARM

POLARITY

NO, NC

NO

In order that the output “DIGITAL OUT 1” gets excited and remains such during all the 
alarm (latching): when the Average Active Power (MEAS 344) falls below the value of 90 
kW, hysteresis 5% and delay of 5 seconds, set the parameters as in the table below:

ALARM 2 / A

MODE (

nota n.2)

Normal, 1-OF-3, 3-OF-3, DERIV, UNBAL

NORMAL

TYPE (

nota n.3)

MAX, MIN

MIN

MEAS (

nota n.4)

Controlled measure. See table n.1 for the 
register selection

344

THRE (

nota n.4)

Threshold value

90000

ALARM 2 / B

HYST

1...100 (%)

5

DELAY

1...99 (seconds)

5

AVG (

nota n.5)

1...99 (seconds)

1

OUT (

nota n.6)

Normal, Hold, Pulse-L, Pulse-S

NORMAL

DIGITAL OUT 2

MODE

PULSE, ALARM, REMOTE

ALARM

POLARITY

NO, NC

NO

Subject to modifi cation without notice. Edition  06-10-2010

Содержание ATTO D4 DC

Страница 1: ...lation The user should only be allowed to access the instrument front panel where the display is located Do not use the digital outputs for protection functions nor for power limitation functions The instrument is suitable only for secondary protection functions The instrument must be protected by a breaking device capable of interrupting both the power supply and the measurement terminals It must...

Страница 2: ...m 1 If Mode Variation Amplitude of the range of integration for the calculation of average from 1 to 99 sec 163 1 I Hysteresis alarm 1 0 99 164 1 I Delay alarm 1 0 99 s bit 0 7 activation delay bit 8 15 deactivation delay 165 2 F Threshold alarm 1 In percentage if Mode Imbalance or Mode Variation Is automatically rounded to the number of digits edited by keyboard 167 1 I Type of measure selection ...

Страница 3: ...ables output function as impulsive ALARM Enables output function as alarm REMOTE Enables output function through Modbus Protocol NO Normally open NC Normally closed NOTE n 9 P IMP Imported Active Power Energy P EXP Exported Active Power Energy NOTE n 10 YES Refered to the primary of the CT NO Refered to the secondary of the CT NOTE n 11 ALARM 1 Alarm associated to the physic output DIGITAL OUT 1 D...

Страница 4: ...m to the terminals marked voltage input on the instrument according to the applicable diagrams that follow Connessioni amperometriche Use SHUNT with a suitable primary range and a 60 o 100 mV secondary Connect the SHUNT to terminals signed with I1 S1 e S2 current input as in the diagram VOLTAGE AND CURRENT CONNECTION S1 S2 S1 S2 S1 S2 A B T 10 11 12 17 18 19 20 U1 U2 U3 N I1 I2 I3 RS 485 AUX AUX V...

Отзывы: