Electrical Control Function
Electrical Control System
91
The digital display tube will display the follow procedure when push SW1 each time.
Display
Remark
0
Normal display
Display running frequency, running state or malfunction code
1
No. of indoor units in good connection
Actual data
2
Outdoor unit running mode code
Off:0,Fan only 1, Cooling:2, Heating:3, Forced cooling:4
3
A indoor unit capacity
The capacity unit is horse power. If the indoor unit is not connected,
the digital display tube will show: “――”
(7K:0.8HP, 9K:1HP,12K:1.2HP,18K:1.5HP)
4
B indoor unit capacity
5
C indoor unit capacity
6
D indoor unit capacity
7
E indoor unit capacity
8
A Indoor unit capacity demand code
Norm value*HP
(7K:0.8HP, 9K:1HP,12K:1.2HP,18K:1.5HP)
9
B Indoor unit capacity demand code
10
C Indoor unit capacity demand code
11
D Indoor unit capacity demand code
12
E Indoor unit capacity demand code
13
Total indoor units amendatory capacity
demand code
Forced cooling:7
14
The frequency corresponding to the total
indoor units amendatory capacity demand
15
The frequency after the frequency limit
16
The frequency sending to compressor
control chip
17
A indoor unit evaporator outlet temp.(T
2B
A)
If the temp. is lower than -9 degree, the digital display tube will show
“-9”.If the temp. is higher than 70 degree, the digital display tube will
sho
w “70”. If the indoor unit is not connected, the digital display tube
will show: “――”
18
B indoor unit evaporator outlet temp.(T
2B
B)
19
C indoor unit evaporator outlet temp.(T
2B
C)
20
D indoor unit evaporator outlet temp.(T
2B
D)
21
E indoor unit evaporator outlet temp.(T
2B
E)
22
A indoor unit room temp.(T
1
A)
If the temp. is lower than 0 degree, the digital display tube will show
“0”.If the temp. is higher than 50 degree, the digital display tube will
show “50”. If the indoor unit is not connected, the digital display tube
will show: “――”
23
B indoor unit room temp.(T
1
B)
24
C indoor unit room temp.(T
1
C)
25
D indoor unit room temp.(T
1
D)
26
E indoor unit room temp.(T
1
E)
27
A indoor unit evaporator temp.(T
2
A)
If the temp. is lower than -9 degree, the digital display tube will show
“-9”.If the temp. is higher than 70 degree, the digital display tube will
show “70”. If the indoor unit is not connected, the digital display tube
will show: “――”
28
B indoor unit evaporator temp.(T
2
B)
29
C indoor unit evaporator temp.(T
2
C)
30
D indoor unit evaporator temp.(T
2
D)
31
E indoor unit evaporator temp.(T
2
E)
32
Condenser pipe temp.(T3)
33
Outdoor ambient temp.(T4)
34
Compressor discharge temp.(T5)
The display value is between 30~129 degree. If the temp. is lower
than 30 degree, the digital display t
ube will show “30”.If the temp. is
higher than 99 degree, the digital display tube will show single digit
and tens digit. For example, the digital display tube show “0.5”,it
means the compressor discharge temp. is 105 degree.)
35
AD value of current
The display value is hex number.
For example ,the digital display tube show “Cd”, it means AD value is
205.
36
AD value of voltage
37
EXV open angle for A indoor unit
Actual data/4.
If the value is higher than 99, the digital display tube will show single
digit and tens digit.
For example ,the digital display tube show “2.0”,it means the EXV
open angle is 120×4=480p.)
38
EXV open angle for B indoor unit
39
EXV open angle for C indoor unit
40
EXV open angle for D indoor unit
Содержание ELAU-VCZ218-H11
Страница 13: ...Indoor Units Indoor Units 11 Part 2 Indoor Units JKD Type 12 Light Commercial 22...
Страница 17: ...Wiring Diagrams Indoor Units 15 3 Wiring Diagrams ELSI JKD009 N11 ELSI JKD012 N11 ELSI JKD018 N11...
Страница 20: ...Exploded View and Spare Part list 18 Indoor Units Exploded View of indoor unit ELSI JKD012 N11...
Страница 22: ...Exploded View and Spare Part list 20 Indoor Units Exploded View of indoor unit ELSI JKD018 N11...
Страница 34: ...Dimensions 32 Indoor Units 2 Dimensions 2 1 Four way cassette type compact 2 2 A5 Duct H G E F A B D C...
Страница 36: ...Dimensions 34 Indoor Units...
Страница 38: ...Service Space unit mm 36 Indoor Units 3 3 Console...
Страница 40: ...Wiring Diagrams 38 Indoor Units ELSI OCD012 N11 ELSI QAD012 N11...
Страница 41: ...Wiring Diagrams Light Commercial 39...
Страница 44: ...Exploded View and Spare Part list 42 Indoor Units Exploded View of indoor unit ELSI OCD012 N11...
Страница 46: ...Exploded View and Spare Part list 44 Indoor Units Exploded View of indoor unit ELSI QAD012 N11...
Страница 52: ...Dimensions 50 Outdoor Units ELAU VCZ536 H11...
Страница 56: ...Wiring Diagrams 54 Outdoor Units 4 Wiring Diagrams ELAU VCZ218 H11 ELAU VCZ327 H11...
Страница 57: ...Wiring Diagr ams Outdoor Units 55 ELAU VCZ430 H11 ELAU VCZ536 H11...
Страница 63: ...Exploded Vi ew and Spare Part list Outdoor Units 61 Exploded View of outdoor unit ELAU VCZ327 H11...
Страница 65: ...Exploded Vi ew and Spare Part list Outdoor Units 63 Exploded View of outdoor unit ELAU VCZ430 H11...
Страница 67: ...Exploded View and Spare Part list 66 Outdoor Units Exploded View of outdoor unit ELAU VCZ536 H11...
Страница 125: ...SERVICE MANUAL Multi Splits Series...