13-1
TROUBLESHOOTING
SM ASP 1-E.2 GB
13. TROUBLESHOOTING
NO
SYMPTON
PROBABLE CAUSE
CORRECTIVE ACTION
1.
The stand-by
indicator (red led)
on the central
control display
panel doesn’t light
up.
There is no correct voltage
between the line and neutral
terminals on main P.C.B
-If the voltage is low repair power
supply.
-If there is no voltage repair
general wiring.
-If there is correct voltage replace
main or display P.C.B’S
2.
The operation
indicator (green
led) on the central
control display
panel does not
light up.
The remote control batteries
are discharged
-Replace batteries of the remote
control.
3.
The operation
indicator (green
led) does not light
up when starting
from unit.
Check main P.C.B and display
P.C.B
-Replace P.C.B if necessary.
4.
The indoor fan
does not function
correctly.
Check the voltage between
indoor fan terminals on the
main P.C.B
-If there is voltage replace
capacitor or motor.
5.
The outdoor fan
does not function
correctly.
Check the voltage between out
door fan terminals on the main
P.C.B
There is voltage between
outdoor fan terminals on the
outdoor unit.
There is no voltage between
outdoor fan terminals on the
outdoor unit.
-If there is no voltage replace main
P.C.B
-Replace capacitor or motor.
-Check and repair electrical wiring
between indoor and outdoor units.
6.
The compressor
does not start up.
Check voltage on compressor
terminals on the outdoor unit.
(with ammeter)
Check if there is correct voltage
between compressor terminals
on the outdoor unit.
-If no voltage replace main P.C.B
-If low voltage repair power supply.
-If the voltage correct replace
capacitor or compressor.
-If there is no voltage repair
electrical wiring between indoor
and outdoor units.
7.
The refrigeration
system does not
function correctly.
Check for leaks or restrictions.
With ammeter. Pressure gauge
or surface thermometer.
-Repair refrigeration system and
charge refrigerant if necessary.
CONTENT
Содержание Alpha 12 SP EU R410A
Страница 16: ...4 1 OUTLINE DIMENSIONS SM ASP 1 E 2 GB 4 OUTLINE DIMENSIONS 4 1 Alpha SP 9 4 2 Alpha SP 12 CONTENT...
Страница 17: ...4 2 OUTLINE DIMENSIONS SM ASP 1 E 2 GB 4 3 Alpha 7 9 Omega 4 4 Alpha 12 Omega CONTENT...
Страница 18: ...4 3 OUTLINE DIMENSIONS SM ASP 1 E 2 GB 4 5 Alpha 9 DF 4 6 Alpha 12 DF 180 680 250 180 250 840 CONTENT...
Страница 57: ...6 6 SOUND LEVEL CHARACTERISTICS SM ASP 1 E 2 GB CSP I 12 RC R410A Cooling CSP I 12 RC R410A Heating CONTENT...
Страница 59: ...8 1 WIRING DIAGRAMS SM ASP 1 E 2 GB 8 WIRING DIAGRAMS 8 1 Indoor Unit ASP9 12 CONTENT...
Страница 60: ...8 2 WIRING DIAGRAMS SM ASP 1 E 2 GB 8 2 Outdoor Unit CSP9 12 CONTENT...
Страница 61: ...9 1 ELECTRICAL CONNECTIONS SM ASP 1 E 2 GB 9 ELECTRICAL CONNECTIONS 9 1 ASP9 12 CSP9 12 CONTENT...
Страница 101: ...14 4 EXPLODED VIEWS AND SPARE PARTS LISTS SM ASP 1 E 2 GB 14 4 Outdoor Unit CSP 9 12 RC R22 CONTENT...
Страница 107: ...14 10 EXPLODED VIEWS AND SPARE PARTS LISTS SM ASP 1 E 2 GB 14 10 Outdoor Unit CSP 9 12 RC R410A EU CONTENT...
Страница 110: ...14 13 EXPLODED VIEWS AND SPARE PARTS LISTS SM ASP 1 E 2 GB 14 13 Outdoor Unit CSP 9 12 ST R410A EU CONTENT...
Страница 120: ...14 23 EXPLODED VIEWS AND SPARE PARTS LISTS SM ASP 1 E 2 GB 14 23 Outdoor Unit CSP 9 12 RC R410A ISR CONTENT...
Страница 123: ...14 26 EXPLODED VIEWS AND SPARE PARTS LISTS SM ASP 1 E 2 GB 14 26 Outdoor Unit GCZ 12 RC R410A ISR CONTENT...