Installing your thermostat

4. Setting the system mode

Press   to change the system mode HEATING, 

COOLING and VENTILATION.  In the mode of 

VENTILATION, the valve is off but the fan runs.

7. Setting functions and options

During power off, press and hold           at the same 

time for 5 sec. to system functions.  Then press  

to change the different items.  

All the settings will confirm automatically when 

     

This product is suitable for standard 86mm wall 

box or european 60mm round box.

1. Connect the wire of power and other equipment into 

    the terminals.

2. Fix the wall plate into the wall box by a screwdriver.

3. Connect the LCD board into the wall plate.

4. Finished.

(Fig 1)

(Fig 2)

(Fig 4)

(Fig 3)

WARNING: 

 Please arrange the professional technician 

to install this product according to installation drawing and 

instruction. 

RISK OF ELECTRICAL SHOCK.

 Disconnect power supply 

before making electrical connection. Contact with components 

carrying hazardous voltage can cause electrical shock and may 

result in severe personal injury or death.instruction. 

5.Selecting manual and programmable

Press and hold     .  Press     to select manual and

     to select weekly programmable.

6. Adjusting the weekly programmable

Then press   to change the different items. 

The order is Minute adjusting→ Hour adjusting

→ 

W

eek adjusting→ Minute timing-on → Hour 

timing-on→ Minute timing-o

f

f→ Hour timing-o

f

f→ 

Temperature adjusting ( 

“12345”,”6”,”7”, is “5+1+1” programmable mode, 

every mode has two times zones and a time 

temperature setting)

Week 

First Period 

Second Period 

Turn-on 

me 

Turn-o

 

me 

Set 

temp. 

Turn-on 

me 

Turn-o

 

me 

Set 

temp. 

Mon. to Fri. 

Sat. 

10 

11 

12 

Sun. 

13 

14 

15 

16 

17 

18 

 

Press     to set minutes of the time;

Press     to set hours of the time;

Press     to set week of the time;

Press     into the adjustment of programmable.

After the above steps, press     into programmable.

Press      or       to set the relative values.            

No 

Func on 

Se ng & Op ons 

Default 

Temp. 

Calibra on 

-9

 to 9

 

 

-2  

 

Fan Control 

 

0: When room temp. reaches 

the setpoint, the fan will turn 

o

1: When room temp. reaches 

the setpoint, the fan will keep 

running.

Lock 

 

0

All the bu ons are locked 

except POWER 

All the bu ons are locked 

Heat/Cool 

0

Cool only      

  1

Heat/Cool 

Min. Set Temp. 

5-15

 

05

Max. Set Temp.  5-35

 

35 

Time Display 

0:12 hours  

1:24 hours 

Display Mode 

 

1

display set temp. only 

0

display both set temp. and

 

room temp. 

 

Wiring your thermostat

L

N

M

Valve

AC220±10%V 50~60Hz

Fan

 

Press       or       to set the relative values.            

power is on.

Remark: Programmable won’t be working for RS485 type.

Two Pipe System

1

 

 

 

 

1-5

 

Cl

ose

M

M

Valve

Cooling 

Valve

Fan

Open

Cl

ose

Ope

n

Lo

w

Me

d

Hi

gh

AC220±10%V 50~60Hz

Four Pipe  System

Close

Open

Lo

w

Me

d

High

L

N

︽ 

 press

Deadzone Temp.