11
A
HOW FUMEREX WORKS: ALARM NOTIFICATION
In the event of smoke/CO detection, the system will cause an alarm and can notify the listed user
phone number by SMS text message.
In the event of alarm, the system will follow this pattern:
• The system switches to Wake-Up mode (see SLEEP AND WAKE-UP MODES).
• The system attempts to send an SMS text message containing alarm text to all listed user
phone numbers simultaneously.
• The system auto-resets the smoke or CO detector when the smoke/CO clears. The system will
not extend the Wake-Up mode period nor deliver any extra SMS text message in case of alarm
recurrence while the Wake-Up mode period is in progress.
• The system may fail to deliver the SMS text message to the listed user phone number due to
the following reasons:
• system or user's phone has been out of GSM signal coverage.
• user’s mobile phone has been switched off.
• The system sends the SMS text message only once and in case of all unsuccessful attempts
within a Wake-Up period, the system will switch to Sleep mode and erase the alarm event
from the memory.
CO related SMS text messages and device indications:
• CO critical level 1
– when CO concentration 30-49ppm remains for more than 120 minutes.
This level causes no audible alarm.
• CO critical level 2
– when CO concentration 50-99ppm remains for more than 60 minutes.
Indicated by a 2-second beep every 5 seconds and red indicator flash.
• CO critical level 3
– when CO concentration 100-299ppm remains for more than 10 minutes.
Indicated by a 2-second beep every 5 seconds and red indicator flash.
• CO critical level 4
– when CO concentration 300ppm and more are reached. Indicated by a
2-second beep every 5 seconds and red indicator flash.
• Fresh air
– when CO level decreases from any critical level to 0-29ppm. This level causes no
audible alarm.
• CO sensor ERROR
– CO sensor has failed. Please contact your local supplier for repair service.
CO sensor lifetime is 7 years.
WHA
T
I SHOULD
KNO
W
EN
Содержание Fumerex
Страница 5: ...5 WHERE TO INSTALL 5 METAL MIN 5 C 41 F MAX 45 C 113 F ES IT FR EN...
Страница 7: ...7 HOW TO INSTALL PIN 3G 2G PIN 3G 2G PIN 3G 2G PIN 3G 2G C ES IT FR EN...
Страница 55: ...55...
Страница 56: ...16 1438 CPR 0455 EN 14604 2005 AC 2008...