background image

Model

WSD01-04A01

Technical data

Supply voltage: 

 max. 11.5 - 20.5 V DC 

via DALI-Bus

Connection: 

 Spring  terminal 

Line 0.2 - 0.75 mm² 

rigid or flexible

Current consumption: 

17 mA 

Operating temperature: 

-20 °C to +60 °C

Dimensions:  

 Key:  55x55x9 mm 

or

 

Keys: 27x55x9 mm 
 Mounting  plate: 

71x71x1.5 mm

Weight: 

30.0 g

System requirements: 

 Windows Vista, 7, 8, 10 

USB 1.1 or higher 

10 MB free hard drive space

 Scope of delivery

DALI module, mounting plate, 1x single-button unit, 2x 

serial button unit, attachment set, operating instructions

Intended use

The device must only be used as a wall-mounted button unit 

for controlling DALI end devices. 
The manufacturer is not liable for any damage caused by 

improper or unintended use!

Safety information

 Before connecting this device, please read these 

instructions carefully! 

Observe any applicable laws, standards and regulations 

as well as manufacturer instructions pertaining to the de-

vices being connected! 
Have any malfunctioning devices inspected by the manu-

facturer! 
Do not perform unauthorised modifications to the device!

Function

The DALI wall-mounted button unit enables up to four DALI 

functions to be triggered via the DALI bus. (DALI: Digital Ad-

dressable Lighting Interface).
When using one-button operating modes, a maximum of four 

DALI devices or four DALI groups can be addressed. 
When using two-button operating modes, the number of ad-

dressable devices or groups is reduced to two.
It is also possible to simultaneously control all devices on the 

DALI bus (broadcast) in any mode. 

WSD01   Wall-mounted button unit DALI

D

The WSD01 DALI wall-mounted button unit can be used as a 

single-button controller or as a serial button controller. 
The "WSD01 Configurator" software is used to allocate indi-

vidual functions to the individual buttons.
Each individual button can have a function allocated to it:
-

DIM two-button operation,

-

ON/OFF two-button operation,

-

DIM one-button operation,

-

ON/OFF one-button operation,

-

Open SCENE,

-

SKIP through scenes,

-

DEAD MAN'S SWITCH one-button operation,

-

Fixed dimmer setting.

The function “DIM two-button operation” is configured as a 

factory preset for broadcasting to all DALI devices on the 

bus.
This enables the wall-mounted button unit to be used on the 

DALI bus without any prior programming using the “WSD01 

Configurator”. 
The RGD-ACC-01 set-up cable (including “WSD01 Configu-

rator”) is required to modify function and address allocations. 

This is not included with the product and must be ordered 

separately.

Connecting the wall-mounted button unit with 

the PC

To enable the DALI wall-mounted button unit to be config-

ured  using  the  PC,  the  RGD-ACC-01  set-up  cable  is  re-

quired (see Figure 1). 
1. Remove the cover panel and the WSD01 from the

mounting plate if necessary.

2. Insert the enclosed programming adapter into the DALI 

end of the set-up cable.

3. Connect the 4-pin programming adapter to the rear of

the WSD01. The connectors are protected from being 

inserted the wrong way around.

4. Insert the USB plug of the set-up cable into a free USB 

port on the PC.

5. Install and launch the "WSD01 Configurator" configu-

ration software.

Single-button 

controller

Serial button 

controller

E

F

A

B1

D

B2
I

(siehe Abb. 1)

A 

Button(s)

B1  DALI module, front
B2  DALI module, rear
D 

 Cover  frame,   

cut-out dimensions 55x55 mm 

(not included in scope of delivery

)

E 

Mounting plate

F Clip
G 

Programming adapter

H 

Programming cable RGD-ACC-01

I 

 Connection terminal (DALI terminals) 

(recommended removal tool: SMDflat WKZ)

PC

 

Fig. 1

Power supply DALI bus

G

 

H

 

Disposal

Waste electronic equipment must not be disposed of 

with household waste!
Dispose of the waste equipment via collection 

facilities for electronic scrap or via your special-

ist dealer.
Dispose of packaging material in the recycling 

bins for cardboard, paper and plastic.

Warranty

Within the statutory warranty period, we undertake to rectify 

free of charge by way of repair or replacement any product 

defects arising from material or production faults.
Any unauthorised tampering or modifications will render this 

warranty null and void.

Conformity

Hereby,  ELDAT  GmbH  declares  that  the  radio  equipment 

type WSD01 is in compliance with Directive 2014/53/EU. 

The full text of the EU declaration of conformity is available 

at the following internet address: www.eldat.de

Customer service

If, despite proper handling, the device does not work prop-

erly or if the device has been damaged, please contact the 

manufacturer or your retailer.
ELDAT GmbH

Im Gewerbepark 14

15711 Königs Wusterhausen / Germany

Phone:  

+ 49 (0) 33 75 / 90 37-310

Fax:  

+ 49 (0) 33 75 / 90 37-90

Internet:   www.eldat.de

Email:  

[email protected]

Preparing the wall-mounted button unit for operation

General information

1. Attach the mounting plate to the installation location

using the enclosed screws & wall plugs or the adhesive 

pads.

2. Connect the WSD01 to the DALI bus via the DALI termi-

nals on the rear. The direction is interchangeable.

3. Place the cover frame on the mounting plate and lock

the DALI module into place at the top and bottom onto 

the clips. The arrow on the module must be pointing 

upwards.

4. Plug  your  chosen  button  unit  (single-button  or  serial 

button controller) onto the transmitter module.

5. (optional)  Program  the  functions  and  addressing  of 

the WSD01 using the RGD-ACC-01 set-up cable and 

"WSD01 Configurator".

Отзывы: