[Fig. 25]
Phase-phase Voltage VL1-L2. It appears only in 2 PH.
4 SETUP PAGES (ALL THE MODELS)
Programming the instrument through the SETUP menu. Use the PAG and SEL keys to access the Programming mode
(SETUP menu).
See also the diagram on page 8 reading this chapter
4.1 SETUP PAGE PROTECTION CODE
By default, the access code to set-up pages is not enabled. To enable it, keep the PAG + SEL keys pressed at the same
time for 30 sec. The display will show the page on which the access code must be entered. [Fig.26].
[Fig. 26]
By means of the SEL + SET keys, every digit can be changed and the code can be entered. The initial
factory code , that must be entered the first time is 000000. Confirm and exit from this page by pressing the
PAG key.
Now a second page (with "COD" blinking), identical to the first one, is displayed:
From this page, the access code can be permanently changed, if wished.
In this case remember or make a safe note of the new code somewhere you can find it later on.
To exit from the second page press the PAG key.
IMPORTANT:
After the first access to the password page, the request of the code will become permanent.
From that moment on the code must be always entered to access the set-up page.
Avoid to recall the password page, for test purposes, if the code request is not permanently desired.
4.2 SETUP PAGES
To access SETUP pages press the PAG and the SEL keys at the same time. Press the PAG key to access the next page,
press the SEL key to select a digit or a setting. Use the SET key to adjust it.
The SETUP can be protected with a password (see paragraph 4.1).
[Fig. 27]
Programming Primary / Secondary of the Voltage Transformers (VT). Use a ratio equal to 1
(e.g. 100/100) in case of direct measures without voltage transformer. Select a digit with the SEL key;
change its value using the SET key.
[Fig. 28]
Programming Primary / Secondary of the Current Transformers (CT). Use a ratio equal to 1 (e.g. 5/5) in
case of direct measures without current transformer. Select a digit with the SEL key; change its value
using the SET key.
[Fig. 29]
Integration Time of the average Power and Current settable from 0 to 99 minutes.
Select a digit with the SEL key; change its value using the SET key.
[Fig. 30]
Energy counters Reset
If you select YES with the SET key, all the counters will be reset as soon you confirm by pressing the
PAG. key.
[Fig. 31]
Reset of the average and maximum demand, Power and e Current.
If you select YES with the SET key, all the counters will be reset as soon you confirm by pressing the
PAG. key.
[Fig. 32]
Enable Cogeneration counters.
Select ON or Off to enable the measures and confirm with PAG
To measure properly the cogeneration counters it is strictly necessary to connect the CTs oriented in
the same direction.
[Fig. 33]
Programming connection type
Select the type of system which you want to measure using the SET key.
Delta = Three phases without neutral (i.e. Delta) (3 PH)
Star = Three phases with neutral (i.e. Star) (3 PH-N)
Diphase = Two-phases with neutral (2 PH)
Single-Phase = Single phase with neutral (1 PH)
VIP ENERGY2K8 PASSWORD SETUP MEMO
Serial Number
Installed At
Factory Password
000000
Date
New Password
Date
New Password
Date
New Password