05/2005 - Art. Nr. 13 018 078A
26
Startup
Adjustment data
The above adjustment data correspond
to the
default settings
. Pre-delivery
adjustment settings appear within a
black rectangle.
These settings allow the burner to be
run in normal operation, but always
carry out a careful check of adjustment
settings, as individual plant conditions
may require certain corrections.
The following nozzles types must be
used to ensure favorable combustion
values:
Danfoss
Steinen
Fluidics
Burner
Burner power
kW
Fuel-oil flow rate
kg/h
Nozzle
Gph 45°B
or 60°B
Pump
pressure
bar
Dimension
Y
mm
Air flap position
1
st
stage
2
nd
stage
1
st
stage
2
nd
stage
1
st
stage
2
nd
stage
1
st
stage
2
nd
stage
Cam IV
Cam I
L 04.410 DUO
190
260
16
22
4.5
11
22
10
17
25
230
330
19
28
5
11
22
15
25
35
260
370
22
31
6
11
22
20
25
40
L 04.500 DUO
210
300
17.5
25
4
2
12
15
17
25
270
390
23
33
5.5
2.5
13
20
25
35
310
440
26
37
6.5
3
11
30
30
40
Содержание VECTRON L 04.410 DUO
Страница 32: ...05 2005 Art Nr 13 018 078A 32 ...
Страница 38: ...05 2005 Art Nr 13 018 078A 38 ...
Страница 45: ......
Страница 46: ...05 2005 Art Nr 13 018 078A 46 ...
Страница 47: ...47 05 2005 Art Nr 13 018 078A ...