Caution:
1. Cut off the main power first
2. Don’t touch LED while maintaining or cleaning
3. Don't use chemical reagent to clean lamp.
Environmental protection: waste electrical products should not be disposed of with household waste. Please recycle
where facilities exist. Check with your local authority or retailer for recycling advice.
Maintenance
1. The product must be installed by professional technicians and power supply must be cut off before installation.
2. The installation wiring must be 0.75mm
2
at least and wired in accordance with the latest IEE electrical
regulations or the national requirements.
3. Do not touch the electronic circuit and its components.
4. Contact an authorised technical service centre for any repairs possibly required use only original spare parts.
5. Do not touch LED while installing or maintaining.
6. The LED light source can not be replaced.
Detection Pattern
ceiling mounting pattern (m)
5m
8m
wall mounting pattern (m)
9m
4m
RoHS
SAA
IP54
TM
Sensor On-off / dimming setting options (For code M320 18 SOF / M320 18 SDM / M320 18 STM)
Hold-time
5s~10min
5m
8m
Stand-by period
0s~+ 8
Detection area can be reduced by selecting the
combination on the DIP switches to fit precisely for
each specific application.
Detection area
I – 100%
II – 50%
1
I
II
50%
100 %
Hold-time means the time period you would like to
keep the lamp on 100% after the person has left the
detection area.
I – 5s
II – 30s
III – 3min
IV – 10min
30s
5s
10min
3
2
I
II
III
IV
3min
I – 0s
II – 30s
III – 10min
IV – +
∞
This is the time period you would like to keep at the
low light output level before it is completely switched
off in the long absence of people.
Stand-by period (corridor function)
I – Disable
II – 50Lux
III – 10Lux
IV – 2Lux
Daylight sensor
The daylight threshold can be set on DIP switches,
to fit for particular application.
5
4
50Lux
10Lux
2 Lux
Disabl
e
I
II
III
IV
30s
0s
+∞
7
6
I
II
III
IV
10min
Hold-time
2~50Lux
Note: “0s” means on/off control;
“+ ” means bi-level dimming control, fixture
never switches off.
8
I – 10%
II – 30%
8
I
II
30%
10%
This is the dimmed low light output level you would
like to have after the hold-time in the absence of
people.
Stand-by dimming level
3
4
AC cables come in through plastic plug, and
are connected to the terminal block.