6.6.6 Zones test

Browse to “Zones test” and press OK.

If no zone is set to “walk test”, a message will appear: press STOP. Otherwise, press OK again to start the test.

Generate alarm conditions for each detector whose “walk test” checkbox in the configuration software has been

flagged by the installer. Every time you successfully generate an alarm condition, a confirmation signal will

sound.

The detectors that have not been successfully tested are listed in the LCD of the keypad. Use the arrow keys to

browse the list.

Once you have verified that all the detectors function properly, or that some are faulty, press STOP twice to exit.

A confirmation signal will sound.

Note:

 If the test is successful, a “Test done” message appears and the “Zones test OK” event is logged.

If you exit the zones test menu while some zones have yet to be tested, the “Zones test failed” event is logged.

6.6.7 Output test

Browse to “Output test” and press OK.

The “ALARM relay +” output is displayed. Press OK to activate it for ~6 s (press STOP to shorten this time). 

The next outputs are shown, “TAMPER relay +” and “SOUNDER relay +”. Press OK as above.

After testing those, the display shows “Output n.---”, select the output you want to test or press STOP to exit.

Note:

 testing the sirens might generate public nuisance. Additionally, if any output is connected to devices that

signal the alarm to a control centre, warn them about the test.

6.6.8 Dialler test

Browse to “Dialler test” and press OK.

Press OK again: the control unit calls the first telephone number (a signal sounds and a message appears).

An error message appears if the dialler is not properly set or the first telephone number is empty.

Press STOP to exit.

Note:

 before testing the dialler, warn the owner of the called number.

Note:

 the test is not available unless at least one telephone number is saved to the control unit.

6.6.9 Battery test

Browse to “Dialler test” and press OK.

Press OK again to start the test. A progress bar will be displayed: [######             ].

Once the progress bar fills, wait at least 2 minutes and press OK to repeat the test, or press STOP to exit.

The results of the battery test can be seen in the Events Log (see “Read the event log” on page 11).

6.6.10 Weekly program

Browse to “weekly program” and press OK.

The display shows the date of tomorrow and the daily program currently set for tomorrow.

Press * or # to cycle through the different daily programs (i.e. holiday; weekday; half holiday A; half holiday B:

four different sets of activation and deactivation times that the installer memorized in the configuration software)

and stop on the daily program you want to use tomorrow.

Press the arrow keys to visualize a different day of the next week (e.g. if today is Friday, from tomorrow to next

Friday) and */# to change those daily programs as well.

Press OK to save the currently selected option for all seven days or STOP to exit without saving.

Содержание TITANIA

Страница 1: ...TITANIA and TITANIAPLUS Intrusion detection control unit with embedded OS 090020692 USER MANUAL IT08020000001624...

Страница 2: ...tremely low percentage of the components used is subjected to faults just as any other electronic or mechanic product As this item is meant to protect both property and people we invite the user to pr...

Страница 3: ...he system keypads e g METIS NIRVA TATTILO TATTILOPLUS ANIMA or MIDAS The system can be divided in 8 separate areas with 4 partialization sectors each each identified by a customized name Internal time...

Страница 4: ...n integrated proximity key reader Up to four other I66 or I7 proximity key readers can be connected directly to the keypad The following image shows the position of these elements on a NIRVA keypad Th...

Страница 5: ...d the configuration software provides for a quicker and finer programming By default the installer can only access the control unit after a user authorizes the access Once authorized if the system adm...

Страница 6: ...ectors assigned to the user Disarming lock disables the system disarming for the user Access control enables the user to Access Control Do not send SMS disables SMS sending when the user arms disarms...

Страница 7: ...ation menu after 30 seconds from the last button pressed command given except where otherwise stated The PROMPT or WELCOME MESSAGE is the standard screen shown on the display when the control unit is...

Страница 8: ...2 USER MANUAL TITANIA v 6 series international elmospa com elmospa com 6 OPERATIVITY Note the examples below use the NIRVA keypad The buttons are shaped differently on different keypads 6 1 General in...

Страница 9: ...a com elmospa com 6 2 User access Despite there being 256 available users only the first 3 are active after a factory reset New users have to be activated by the installer using the configuration soft...

Страница 10: ...exclusion of zones If the installer flagged some zones for automatic exclusion the user will be able to arm the system area even if any of these zones is in anomaly condition The affected zone will be...

Страница 11: ...1 You are now inside a list of zones positioned at the chosen one Use the arrow keys to cycle through the list Press OK to bypass the currently shown zone or to include it again then STOP to go back...

Страница 12: ...y output is connected to devices that signal the alarm to a control centre warn them about the test 6 6 8 Dialler test Browse to Dialler test and press OK Press OK again the control unit calls the fir...

Страница 13: ...pressure of delays the arming by a time set by the installer up to a maximum delay that has also been set by the installer Press to reset the delay Press OK to save and STOP to exit Note an error mess...

Страница 14: ...nomaly for each test that has yet to be passed Once all tests have been successfully run the system anomaly LED turns off Note the installer shall modify the System test timer only if the user require...

Страница 15: ...rming with automatic exclusion of alarmed zones 10 6 3 2 System or area arming with forced exclusion of alarmed zones 10 6 4 MAX SECURITY system arming 10 6 5 System or area disarming 10 6 6 Basic Mai...

Страница 16: ...AL October 2017 edition 090020692 The information and product features herein are not binding and may be changed without prior notice EL MO SpA Via Pontarola 70 35011 Campodarsego PD Italy Tel 3904992...

Отзывы: