When using the optional enclosure
system:
Scenario G)
Stove in enclosure system using
rear-vertical flue adaptor and 4” twin-wall
insulated flue. Enclosure is orientated towards a
wall behind:
see
Figure 3.2.1
-If it is necessary to use a short length of single
skin pipe first, then the distance to rear of
enclosure, from the wall should be increased to
50mm minimum.
See
Figure 3.2.2
Figure 3.1.6
Figure 3.2.1
Figure 3.2.2
Scenario H)
Stove in enclosure system using
rear-vertical flue adaptor and either single
skin or insulated flue. Enclosure is in a corner
position at 45 degree angles to each wall:
see
Figure 3.2.3
Scenario I)
Stove in enclosure system using top
flue outlet and either single skin or insulated flue.
Enclosure is in a corner position at 45 degree
angles to each wall:
see
Figure 3.2.4
When there is a requirement to
position the stove closer than
these minimum clearances from
combustibles:
In the event that the above safe distances to
combustibles cannot be achieved, additional
heat-shields can be attached to the wall,
allowing the stove to sit much closer to adjacent
walls.
Consult your installer, speak to Ekol, or consult
the relevant HETAS guidance.
Figure 3.2.3
Figure 3.2.4