3
i
First access
When you open the browser at the default address, the
following login screen is displayed:
This specific functionality does not require any configu
-
ration in KONNECT4, and can be easily reached with a
standard KNX communication driver offered by Control4.
Configuration and commissioning
The configuration and commissioning of the Konnect4
server must be carried out by accessing the web server
integrated in the product. These activities must be carried
out in accordance with the design of the building automa
-
tion system carried out by a qualified professional.
Network connection
The configuration and use of the Konnect4 server requi
-
res a connection to the home or company network. The
default IP address of the delégo server is:
192.168.0.110
For the initial configuration of the server, as well as in
case of absence of a network during the installation pha
-
se, it is necessary to proceed as follows:
•
connect the server Konnect4 to your PC via a “cross
over” (or “crossover”) network cable
•
access your PC’s network settings, as illustrated in
your operating system documentation
•
Change the TCP/IP communication protocol settings
(version 4) for the LAN port of your PC, and set the
following parameters manually:
•
IP address: 192.16 8.0.100
•
Network mask: 255.255.255.0
•
Default gateway: 192.168.0.1
•
Save and wait for the new settings to take effect.
If prompted, reboot the system.
After these operations, open an Internet browser and type
in the address bar:
http://192.168.0.110
Connection as IP gateway for Control4
KONNECT4 can be used as IP gateway for CONTROL4,
in order to make the COMPOSER PRO to communicate
with KNX devices.
User
Password
Description
admin
admin
Automation system
administrator user.
He has the rights
to create users,
manage their rights
and configure the
supervision
user
user
Basic user. It
has the rights to
view the system
status, navigate the
supervision pages
and perform basic
commands on the
automation system
For an optimal browsing experience, we recommend
using one of the following browsers:
•
Google Chrome
•
Apple Safari
Konnect4 server has the following preset users at the
factory:
Enter the credentials of the user “admin” and confirm to
access the main screen of the Konnect4 administration
environment.
Restore factory IP address
If necessary, you can restore the factory IP address of
the server Konnect4 using the RESET button available.
Follow the procedure below:
•
open the front panel of the server Konnect4 using a
small slotted screwdriver, and exerting a slight leverage
effect in one of the side slots
•
locate the RESET button on the back of the vertical
card
•
press the button for at least 10 seconds until the SER
-
VICE LED on the front of the device starts flashing,
then release the button
•
within the next 5 seconds, press and release the button
for 1 second; within a couple of seconds the front LED
will light up solidly for a couple of seconds
•
when the LED goes out, the device can be reached at
the factory IP address (192.168.0.110)
If the LED goes out after long press (10 seconds) before
short press, repeat the whole procedure. This procedure
resets the IP address and retains all data relating to the
configuration previously carried out on the automation sy
-
stem.
Restore factory configuration
If the configuration made makes it impossible to access
the server Konnect4 or its correct use, it is possible to
restore the factory conditions, resetting the IP address