Ekinex EK-HE1-TP Скачать руководство пользователя страница 3

3

•  rotate the device towards the rail (3);

•  push the locking device upward until it stops (4).
Before removing the device, be sure that power supply 

and controlled loads have been disconnected and the bus 

terminal has been extracted from its slot. Use a screwdri-

ver to slide down the locking device and remove the de-

vice from the rail.

Connection of the KNX bus line

The connection of the KNX bus line is made with the ter-

minal block included in delivery and inserted into the slot 

at the bottom of the housing.
Characteristics of the KNX terminal block
•  spring clamping of conductors

•  4 seats for conductors for each polarity

•  terminal suitable for KNX bus cable with single-wire 

conductors and diameter between 0.6 and 0.8 mm

•  recommended wire stripping approx. 5 mm

•  color codification: red = + (positive) bus conductor, 

black = – (negative) bus conductor

1

2

4

3

EKINSTGUIDAEKAB1TP

Note.

 When mounting the device in boards and ca-

binets it shall be provided the necessary ventilation 

so that the temperature can be kept within the ope-

rating range of the device.

i

DCEKHE1TP

+

-

KNX 

Bus

Dev.

Line

Area

bus KNX

1A

2

1

4

3

1B

2A

2B

3A

10

9

12

11

3B

4A

4B

6

5

L

8

7

N

14

13

16

15

L

N

N

N

Warning!

 In order to supply the KNX bus lines use 

only KNX bus power supplies (e.g. ekinex EK-AB1-

TP or EK-AG1-TP). The use of other power supplies 

can compromise the communication and damage 

the devices connected to the bus.

!

Warning!

 The electrical connection of the device 

can be carried out only by qualified personnel. The 

incorrect installation may result in electric shock or 

fire. Before making the electrical connections, make 

sure the power supply has been turned off.

!

Connection of the power supply

The connection of the 230 Vac or 24 Vac power supply is 

made with the screw terminals (L, N) located at the top 

front of the device.
Characteristics of the terminals
•  screw clamping of conductors

•  maximum cross section of conductor 2,5 mm²

•  recommended wire stripping approx. 6 mm

•  torque max 0,5 Nm

Warming!

 The number of electrothermal actuators 

that can be connected in parallel to each output is 

limited by the rated current and the starting current 

of the device. Carefully check the information on 

the technical documentation of the manufacturer of 

actuators. 

!

Connection of the outputs

The connection of the outputs is made with the screw ter-

minals located at the top front of the device.
Characteristics of the terminals
•  screw clamping of conductors

•  maximum cross section of conductor 2.5 mm² (single-

wire) or 1.5 mm² (multi-wire)

•  recommended wire stripping approx. 6 mm

•  torque max 0.8 Nm

To  reduce  the  total  starting  current,  in  case  of  simulta-

neous activation of two or more output channels, it is pre-

ferable to enable the delayed start function during confi-

guration via the ETS; in this case, each output channel 

is activated with a delay time after the previous channel. 

The delay is adjustable in the range 5 ... 40 s and is equal 

for all channels.

Dev.

Line

Area

bus KNX

1A

2

1

4

3

1B

2A

2B

3A

10

9

12

11

3B

4A

4B

6

5

L

8

7

N

14

13

16

15

L

N

N

N

Connection in 4-pipe systems

L

N

230 Vac or

24 Vac

1 2

Valve actuator

(heating)

1 2

Valve actuator

(cooling)

Отзывы: