background image

1

DALI 2 standard dimmers at 12 / 48 Vdc 

with 1 / 2 - channels

Codes: EK-GD2-DL-1-LV, EK-GD2-DL-2-LV

Main functional characteristics

• 

Memory  function  configurable  via  DALI  bus:  it  stores 

the last brightness level, in case of power failure

• 

Soft switching on and off

• 

Brightness adjustment to full power off (dim-to-dark)

• 

Min. brightness level: 0.1% (1% with push for 1 CH)

• 

DALI-settable  dimming  curve:  linear/logarithmic  for 

1CH, 2 CH, linear/quadratic/exponential for 4 CH

• 

On and off times settable via DALI

• 

Control inputs: N.O. push button (for EK-GD2-DL-1-LV 

only), DALI

• 

Optimized output curve

• 

Button for mode change and / or DT6 / DT8 selection 

(depending on the device version)

• 

Status LED (switch to stand-by after 1 min.)

DALI 2 bus dimmer with 12/48 Vdc voltage supply and 1 

or 2 channels, with brightness of LED sources control and 

dimmable in PWM modulation.

Datasheet STEKGD2DL12LV_EN

Note:

 the 1-CH device factory default values are: 

automatic detection of the local command set to 

N.O. pushbutton and minimum dimming value set 

to 1%.

i

Description

The ekinex dimmers DALI 2 standard with 1 / 2-channels 

EK-GD2-DL-1-LV and EK-GD2-DL-2-LV allow brightness 

control of LED loads from 12 to 48 Vdc in constant volta

-

ge, dimmable in PWM modulation.

• 

The 1 CH model is DALI DT6 only and equipped with a 

local control device (N.O. button), connected directly to 

the dedicated input, with stand-alone or status update 

function on the DALI bus.

• 

the 2 CH model can be configured with a single DT6 

output channel, 2 single DT6 channels or a single chan

-

nel in TW DALI DT8 mode.

DT6 / DT8 setting for EK-GD2-DL-2-LV model is done via 

local selector switch. The devices have an integrated bus 

communication module DALI 2 certified.

Technical data

Inputs

• 

Input (constant voltage): 12 / 48 Vdc

• 

Supply voltage: min: 10.8 Vdc .. max: 52.8 Vdc

• 

Power  absorbed  while  awaiting  command:  <500  mW 

(for EK-GD2-DL-1-LV only)

• 

DALI 2 bus input compliant with IEC 62386

Outputs

• 

Output voltage PWM 12 / 48 Vdc

• 

Output current: from 0 A to 10 A for 

EK-GD2-DL-1-LV, 

5A on each channel for 

EK-GD2-DL-2-LV

• 

Rated power @12V: 120 W

• 

Rated power @24V: 240 W

• 

Rated power @48V: 480 W

• 

Command supply current (EK-GD2-DL-1-LV only): 0.5 

mA (for 1-10V)

• 

Command  required  max.  current  (EK-GD2-DL-1-LV 

only): 0.1 mA (for 0-10V)

Warning! Dimmers require the use of a power 

supply in accordance with EN 61347-2-13, such 

as the Mean Well mod. HLG-480H-24A.

!

Note:

 values for output current and nominal power 

have to be intended as maximum values, depen-

ding on the ventilation conditions. The reported 

values are measured with a room temperature of 

40 °C

i

Dimming

• 

“Flicker-free” PWM modulation: 2000Hz f

• 

PWM resolution: 16 bit

• 

PWM dimming range: 0.1-100% for 

EK-GD2-DL-1-LV, 

1-100% for EK-GD2-DL-2-LV

Environmental conditions and other characteristics

• 

Operating temperature: -20 ° C ... + 40 ° C

• 

Storage temperature: - 40 ° C ... + 60 ° C

• 

Transport temperature: - 40 ° C ... + 60 ° C

• 

Maximum case temperature (t

c

): 80 °C

• 

Relative humidity: 93% non-condensing

• 

Protection degree IP10 (device installed)

• 

Wiring: 1.5 mm

2

 solid – 1.0 mm

2

 stranded, 16-17 AWG

• 

Stripping: 5.0 - 6.0 mm

• 

Housing in plastic material

• 

Device  suitable  for  installation  in  flush-mounting  wall 

boxes

Содержание EK-GD2-DL-1-LV

Страница 1: ...a single DT6 output channel 2 single DT6 channels or a single chan nel in TW DALI DT8 mode DT6 DT8 setting for EK GD2 DL 2 LV model is done via local selector switch The devices have an integrated bus communication module DALI 2 certified Technical data Inputs Input constant voltage 12 48 Vdc Supply voltage min 10 8 Vdc max 52 8 Vdc Power absorbed while awaiting command 500 mW for EK GD2 DL 1 LV o...

Страница 2: ...k or DT6 DT8 selector 5 PUSH N O pushbutton pole 1 PUSH N O pushbutton pole 2 EK GD2 DL 1 LV only EK GD2 DL 2 LV only Accessory for 1 CH and 2 CH models Rail mounting support The devices EK GD2 DL 1 LV and EK GD2 DL 2 LV can be mounted on 35 mm rail according to EN 60715 with the plastic support included in the delivery Control signaling and connection elements The devices are equipped with screw ...

Страница 3: ...hort circuit protection only and the power must be correctly dimensioned In case of usage of a po wer supplier with ground terminals all points of the pro tective earth PE Protection Earth must be connected to a valid and certified protection earth Insert the mounting support in the appropriate shaped profile of the back side of the device then hook the teeth to the profile guide starting from the...

Страница 4: ...ue to indicate the programming of the outputs as 2 single channels DALI DT6 pressing the button again will cause the yellow LED to light up indicating that the programming of the outputs is in Tunable White dynamic white with 1 DALI DT8 channel with a long press of at least 5 s the configuration is saved and the menu is exited after 60 s without further pressing the programming key the device exit...

Страница 5: ...n on the DALI bus update the device The software can be downloaded from the website www ekinex com and its use is described in the application ma nual of the ekinex EK BG1 TP DALI Gateway The sof tware works with Microsoft Windows 7 and later DT6 with single output channel DT6 with 2 independent output channels DT8 with single Tunable White output channel DALI System fail function For each device ...

Страница 6: ...ranty period In case of tampering the compliance with the essential requirements of the applicable directives for which the device has been certified is no longer guaranteed ekinex defective devices must be returned to the ma nufacturer at the following address Ekinex S p A Via Novara 35 I 28010 Vaprio d Agogna NO Italy Other information The instruction sheet must be delivered to the end cu stomer...

Отзывы: