9.3 Weighted temperature value
The
Weighted temperature value
folder appears only if two sensors for measuring the room temperature are enabled
and includes the following parameters:
•
Relative weight
•
Minimum change of value to send [K]
•
Cyclic sending interval
9.3.1 Parameter and communication object tables
Parameter name
Conditions
Values
Relative weight
100% main sensor
90% / 10%
80% / 20%
70% / 30%
60% / 40%
50% / 50%
40% / 60%
30% / 70%
20% / 80%
10% / 90%
100% sensor from bus
Minimum change of value to send [K]
0,5
[other values in the range 0 … 5 K]
If the parameter is set to 0 (zero), no value is sent at the change.
Cyclic sending interval
no sending
[other values in the range 30 s … 120 min]
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj. No.
Weighted temperature
Cyclic sending interval ≠ no
sending
2 Byte
CR-T--
[9.001]
temperature °C
19
About weighted temperature
The device allows the acquisition of the room temperature in two ways:
1)
from the temperature sensor integrated in the device;
2)
via bus from another KNX device, e.g. from an ekinex pushbutton (External sensors (from bus) Room
temperature = enabled);
To optimize or correct the room temperature regulation in special cases (in large rooms, in presence of strong
asymmetry of the temperature distribution, when the installation of the device is in a position not suitable, etc.), the
device can then use a weighted average between two temperature values. The weights are assigned by the
parameter
Relative weight
that assigns a ratio of the two values