Applicatio Manual
Universal Interface 4 DIN/NTC EK- CG2-TP
Revisione 1.0.0 - Aggiornato: 04/09/2017
© SBS S.p.A.
– Tutti i diritti riservati
MAEKCG2TP_EN
Pag. 37
9.1.4 Independent or single: dimming
Parameter name
Conditions
Values
Long press time
Input x = independent or single
Type = dimming
hh:mm:ss.fff
(
00:00:03.000
)
Minimum push time for a press in order to be recognized as a long press.
Toggle mode
Input x = independent or single
Type = dimming
enabled /
disabled
When enabled, causes the short press to toggle the on-off status of the destination CO; otherwise, a
fixed status can be assigned to the short press.
Long action
Input x = independent or single
Type = dimming
Toggle mode = enabled
darker
brighter
darker ↔
brighter
Defines the function to be assigned to the long press. If the toggle mode is enabled, the Short press
action is already defined as toggle.
Short / Long action
Input x = independent or single
Type = dimming
Toggle mode = disabled
off / darker
on / brighter
off / darker ↔
brighter
on / darker ↔
brighter
Defines the function to be assigned to the long and short press.
Send cyclically
Input x = independent or single
Type = dimming
none
off / value 1
on / value 2
both off and on / both values
Defines which of the values, if any, must be cyclically retransmitted whenever activated.
Cyclic sending interval
Input x = independent or single
Type = dimming
Send cyclically ≠ none
hh:mm:ss (
00:02:00
)
Interval between cyclical transmissions.
Lock function
–
Behaviour at locking
Input x = independent or single
Type = dimming
none
off
on
toggle
Value to be assigned to the object when a locking command is received.
Lock function
–
Behaviour at unlocking
Input x = independent or single
Type = dimming
none
off
on
as previous
Value to be assigned to the object when an unlocking command is received.