INDICATION
The device has a LED which indicates its state according to the following:
TESTING
To test the device, activate an alarm condition on the system via a call-point or fire
sensor. The sounder should activate with the selected tone and volume.
To stop the test silence and reset the control panel.
АNALOG DATA
The device provides the translator module with analog data about air temperature
and voltage levels on its batteries. This information can be viewed in the “Ekho
Configiurator
” software.
By analyzing the voltage levels, you can manage maintenance procedures and
predict when you will have to replace the batteries.
WARNINGS & LIMITATIONS
Devices use high quality electronic components and plastic materials that are highly
resistant to environmental deterioration. However, after 10 years continuous
operation it is advisable to replace them to reduce the risk of reduced performance
caused by external factors. Ensure the devices are only used with compatible
control panels. Detection systems must be checked, serviced and maintained on a
regular basis to confirm correct operation.
Refer to and follow National Codes of Practice and other internationally recognized
fire engineering standards. Appropriate Risk Assessment should be carried out
initially to determine correct design criteria and updated periodically.
LED indication
Device’s state
No indication or green flashes
Standby mode
Yellow flashes every 4 seconds
Fault state
– low battery
Frequent red flickering
Device is activated