GuaRdboX
-
GP
series
IOM
(
Installation, Operating & Maintenance Manual) 0002-ENG
rev.2
6
Eisenbau s.r.l. a socio unico
Via T.A:Edison, 16 20090 Cusago (MI) Italy
Phone : +390293562116 Fax: +390293567735
Guardbox production unit : Via XXIV Maggio, 13
25017 – Sedena di Lonato (BS)
Phone : +390309131240 Fax: +390309130946
www.eisenbau.it
www.guardbox-ex.com
Pi / PN
(inductive
proximity) /
(inductive proximity
namur)
Board assembly
Turn the actuator pinion full CW
and regulate the cam till the switch
(1) is activated
Turn the actuator pinion full CCW
and regulate the cam till the switch
(2) is activated
Turn the actuator pinion full CW
and regulate the cam till the switch
(1) is activated
Turn the actuator pinion full CCW
and regulate the cam till the switch
(2) is activated
Turn the actuator pinion full CW
and regulate the cam till the switch
(1) is activated
Turn the actuator pinion full CCW
and regulate the cam till the switch
(4) is activated
Turn the actuator pinion full CW
and regulate the cam till the switch
(1) is activated
Turn the actuator pinion full CCW
and regulate the cam till the switch
(2) is activated
9.
indicator setting:
9.1
The 3D indicator (2) is visible on all 4 sides and is fully adjustable on 360°
without disassembly.
9.2
Loosen indicator M5 captive screws and rotate transparent indicator dome
(1) to desired viewing angle according to valve position. (OPEN or CLOSED
appearing through indicator window).
9.3
Retighten the four captive M5 screws (3) using a torque of 3,5Nm.
3,5Nm