ROUTINE MAINTENANCE 

 

 
 
 
 
 
 
 
To  ensure  continued  full  efficiency  of  the  dehumidifier,  maintenance 
procedures should be performed as follows: 
 

 

 

 

1. 

Clean the surface of the evaporator and condenser coils by blowing 
the  dirt  out  from  behind  the  fins  with  compressed  air.    Hold  the 
nozzle of the air hose away from the coil to avoid damaging the fins.  
Alternatively, vacuum clean the coils. 

 

 
 
 
 

 
 

2. 

Check that the fan is firmly secured to the motor shaft and that the 
fan rotates freely.  

The fan motor is sealed for life and therefore 

does not need oiling.

 

 

 

3. 

To  check  the  refrigerant  charge,  run  the  unit  for  15  minutes  and 
briefly  remove  the  evaporator  filter  cover.    The  evaporator  coil 
should  be  evenly  frost  coated  across  its  surface.    At  temperatures 
above  80

°

F,  the  coil  may  be  covered  with  droplets  of  water  rather 

than  frost.    Partial  frosting  accompanied  by  frosting  of  the  thin 
capillary tubes, indicates loss of refrigerant gas or low charge. 

 
 

4. 

Check all wiring connections. 

  

 

To  check  the  operation  of  the  defrost  system,  switch  the  machine 
on and leave it running for approximately 55 minutes.  The machine 
will then enter “Hot Gas” defrost mode for approximately 5 minutes 
before returning to normal operation.  If the unit will not defrost, the 
printed  circuit  timer  board  may  be  defective  or  the  by-pass  valve 
may be inoperable.  

 
 

I

F ANY OF THE PRECEDING PROBLEMS OCCUR

,

 CONTACT THE 

E

BAC 

S

ERVICE 

C

ENTER PRIOR TO CONTINUED OPERATION OF THE UNIT TO 

PREVENT PERMANENT DAMAGE

.

   

 

WARNING: 

ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN 

DISCONNECTED BEFORE CARRYING OUT ROUTINE 

MAINTNENANCE 

WARNING:

 

DO NOT STEAM CLEAN REFRIGERATION COILS 

Содержание TPC380

Страница 1: ...PC380 Issue 2 Date 03 10 11 ECO150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk To Buy Contact Sylvane at 800 934 9194 or visit www sylvane com For Product Support Contact Ebac Industrial Pro...

Страница 2: ...2 of 13 Drawing TPC380 Issue 2 Date 03 10 11 UNIT PACKAGE CONTENTS Item Description Quantity 10531GR US Dehumidifier 1 3086144 Quick release hose coupling 1 3944110 PVC Tube 3 8 I D 7 8M TPC380 Manua...

Страница 3: ...ent drain The cooled air then passes through the hot condenser coil where it is reheated using the same energy removed during the cooling phase plus the additional heat generated by the compressor The...

Страница 4: ...used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data label MODE...

Страница 5: ...aporator coil ii If the air temperature is above 80 F frost and or droplets of condensed water should cover the entire evaporator coil F After continuous running time of approximately 55 minutes the u...

Страница 6: ...frost coated across its surface At temperatures above 80 F the coil may be covered with droplets of water rather than frost Partial frosting accompanied by frosting of the thin capillary tubes indicat...

Страница 7: ...he refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing...

Страница 8: ...nsufficient air flow 2 Compressor fault 3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required...

Страница 9: ...sor 3944932 1 7 Run Capacitor 3030908 1 8 Solenoid Coil 3030453 1 9 Filter 2053119 1 10 Mains Lead 3031202 1 11 Fan Motor 3040262 1 12 Fan Motor Inlet Ring 3040254 1 13 Fan Motor Capacitor 3030893 1 1...

Страница 10: ...WRITTEN OR IMPLIED WARRANTY WITH RESPECT TO THE FOREGOING DESCRIBED MERCHANDISE For Your Records Model ____________________ S N ______________________ Date Received ______________ SAVE THIS SECTION FO...

Страница 11: ...Page 11 of 13 Drawing TPC380 Issue 2 Date 03 10 11...

Страница 12: ...Page 12 of 13 Drawing TPC380 Issue 2 Date 03 10 11...

Страница 13: ...8 662590 www eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 36...

Отзывы: