TROUBLESHOOTING
S
YMPTOM
C
AUSE
R
EMEDY
Little or no airflow
1. Loose fan on shaft
2. Fan motor burnt out
3. Dirty refrigeration coils
4. Loose electrical wiring
5. Control humidistat either
set too high or
malfunctioning
1. Tighten fan
2. Replace the fan motor
3. See
Routine Maintenance
Section
4. Check the wiring diagram
to find fault and repair
5. Adjust humidistat as
required or replace
Little or no water
extraction
1. Insufficient air flow
2. Compressor fault
3. Loss of refrigerant gas
1. Check all of the above
2. Contact the Factory
Service Center
3. Contact the Factory
Service Center
Little or no defrost
when required
1. Faulty Timer
2. Faulty bypass timer
1. Contact the Factory
Service Center
2. Contact the Factory
Service Center