Should an electrical component fail, consult the Factory Service Center
to obtain the proper replacement part.
I
F ANY OF THE PRECEDING PROBLEMS OCCUR
,
CONTACT THE
E
BAC
I
NDUSTRIAL
P
RODUCTS
L
TD
S
ERVICE
C
ENTER PRIOR TO CONTINUED
OPERATION OF THE UNIT TO PREVENT PERMANENT DAMAGE
.
TROUBLESHOOTING
S
YMPTOM
C
AUSE
R
EMEDY
Little or no
dehumidification
capacity
Filter clogged
Clean or replace filters
No regeneration heat
Check Heaters / OHP
Reduced airflow
Check fans / duct
No rotation of Rotor
Check belt tension / drive motor
Air leakage
Check sealing
Dehumidifier does
not start
No power
Check fuse
Correct switch setting
Check Auto / Manual switch
Loose electrical wiring
Check wiring diagram - fault
find & repair
Rotor does not
rotate
Drive belt slipping
Check belt tension
Drive belt broken
Replace drive belt
Rotor jammed
Check centre shaft, rim of rotor
Drive motor faulty
Check supply /Replace motor
No Dry or Wet Air
Airflow
Filter clogged
Clean or replace filters
Fan faulty
Check supply / fan
Ducts blocked
Check duct for obstruction
Noisy
Fan loose
Check fans secured firmly
Loose fastenings
Tighten all fastenings